کلید حرارتی GV3L25
- برند اشنایدر الکتریک
- مشخصات فنی: Motor circuit breaker, TeSys Deca, 3P, 25 A, magnetic, rotary handle, EverLink terminals
- موجود در ولتابین
- ارسال به سراسر کشور
Range TeSys Deca Product name TeSys GV3
TeSys DecaProduct or component type Motor circuit breaker Device short name GV3L Device application Motor protection Trip unit technology Magnetic Poles description 3P Network type AC Utilisation category Category A conforming to IEC 60947-2 Network frequency 50/60 Hz Fixing mode 35 mm symmetrical DIN rail: clipped
Panel: screwed (with 3 x M4 screws)Motor power kW 11 kW at 400/415 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
18.5 kW at 690 V AC 50/60 HzBreaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz
100 kA Icu at 400/415 V AC 50/60 Hz
50 kA Icu at 440 V AC 50/60 Hz
12 kA Icu at 500 V AC 50/60 Hz
6 kA Icu at 690 V AC 50/60 Hz[Ics] rated service short-circuit breaking capacity 100 % at 230/240 V AC 50/60 Hz
100 % at 400/415 V AC 50/60 Hz
100 % at 440 V AC 50/60 Hz
50 % at 500 V AC 50/60 Hz
50 % at 690 V AC 50/60 HzControl type Rotary handle [In] rated current 25 A Magnetic tripping current 350 A [Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2 Suitability for isolation Yes conforming to IEC 60947-1 Power dissipation per pole 8 W Mechanical durability 50000 cycles Electrical durability 50000 cycles for AC-3 at 415 V In Tightening torque 5 N.m – on screw clamp terminal Width 55 mm Height 132 mm Depth 136 mm Net weight 0.96 kg Colour Dark grey Standards EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1Product certifications CCC
UL
CSA
EAC
LROS (Lloyds register of shipping)
BV
ABS
DNV-GL
UKCAIP degree of protection IP20 conforming to IEC 60529 Climatic withstand Conforming to IACS E10 Ambient air temperature for storage -40…80 °C Fire resistance 960 °C conforming to IEC 60695-2-11 Ambient air temperature for operation -20…60 °C Mechanical robustness Shocks: 15 Gn for 11 ms contactor open
Shocks: 30 Gn for 11 ms contactor closed
Vibrations: 4 Gn, 5…300 HzOperating altitude 3000 m Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 16.000 cm Package 1 Width 6.500 cm Package 1 Length 14.500 cm Package 1 Weight 996.000 g Unit Type of Package 2 P06 Number of Units in Package 2 60 Package 2 Height 75.000 cm Package 2 Width 60.000 cm Package 2 Length 80.000 cm Package 2 Weight 72.760 kg
نقد و بررسیها
هنوز بررسیای ثبت نشده است.