range of product Easy Altivar 610 product or component type Variable speed drive product specific application Fan, pump, compressor, conveyor device short name ATV610 variant Standard version product destination Asynchronous motors mounting mode Cabinet mount EMC filter Integrated conforming to EN/IEC 61800-3 category C3 with 50 m IP degree of protection IP20 type of cooling Forced convection supply frequency 50…60 Hz +/-5 % network number of phases 3 phases [Us] rated supply voltage 380…460 V – 15…10 % motor power kW 110 kW for normal duty
90 kW for heavy dutymotor power hp 150 hp for normal duty
125 hp for heavy dutyline current 201 A at 380 V (normal duty)
175.7 A at 460 V (normal duty)
170 A at 380 V (heavy duty)
149.1 A at 460 V (heavy duty)prospective line Isc 50 kA apparent power 140.0 kVA at 460 V (normal duty)
118.8 kVA at 460 V (heavy duty)continuous output current 211 A at 2.5 kHz for normal duty
173 A at 2.5 kHz for heavy dutymaximum transient current 232 A during 60 s (normal duty)
260 A during 60 s (heavy duty)asynchronous motor control profile Variable torque standard
Optimized torque mode
Constant torque standardoutput frequency 0.0001…0.5 kHz nominal switching frequency 2.5 kHz switching frequency 1…8 kHz adjustable number of preset speeds 16 preset speeds communication port protocol Modbus serial option card Slot A: communication card, Profibus DP V1
Slot A: digital or analog I/O extension card
Slot A: relay output cardoutput voltage <= power supply voltage motor slip compensation Can be suppressed
Adjustable
Not available in permanent magnet motor law
Automatic whatever the loadacceleration and deceleration ramps Linear adjustable separately from 0.01 to 9000 s
S, U or customizedbraking to standstill By DC injection protection type Thermal protection: motor
Motor phase break: motor
Thermal protection: drive
Overheating: drive
Overcurrent between output phases and earth: drive
Overload of output voltage: drive
Short-circuit protection: drive
Motor phase break: drive
Overvoltages on the DC bus: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Line supply phase loss: drive
Overspeed: drive
Break on the control circuit: drivefrequency resolution Display unit: 0.1 Hz
Analog input: 0.012/50 Hzelectrical connection Control, screw terminal: 0.5…1.5 mm²
Line side, screw terminal: 2 x 50…3 x 120 mm²
Motor, screw terminal: 3 x 50…3 x 120 mm²connector type 1 RJ45 (on the remote graphic terminal) for Modbus serial physical interface 2-wire RS 485 for Modbus serial transmission frame RTU for Modbus serial transmission rate 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial type of polarization No impedance for Modbus serial number of addresses 1…247 for Modbus serial method of access Slave supply External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protectionlocal signalling 2 LEDs for local diagnostic
1 LED (yellow) for embedded communication status
2 LEDs (dual colour) for communication module status
1 LED (red) for presence of voltagewidth 320 mm height 852 mm
1159 mm with IP21 conformity kitdepth 390 mm net weight 82 kg analogue input number 3 analogue input type AI1, AI2, AI3 software-configurable voltage: 0…10 V DC, impedance: 30 kOhm, resolution 12 bits
AI1, AI2, AI3 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits
AI2, AI3 software-configurable temperature probe or water level sensordiscrete input number 6 discrete input type DI1…DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm
DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)input compatibility DI1…DI6: logic input level 1 PLC conforming to EN/IEC 61131-2
DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68discrete input logic Positive logic (source): DI1…DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1)
Negative logic (sink): DI1…DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1)
Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1)analogue output number 2 analogue output type Software-configurable current AQ1, AQ2: 0…20 mA, resolution 10 bits
Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bitssampling duration 5 ms +/- 0.1 ms (AI1, AI2, AI3) – analog input
2 ms +/- 0.5 ms (DI1…DI6)configurable – discrete input
5 ms +/- 1 ms (DI5, DI6)configurable – pulse input
10 ms +/- 1 ms (AQ1, AQ2) – analog outputaccuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
+/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog outputlinearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
AQ1, AQ2: +/- 0.2 % for analog outputrelay output number 3 relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000 cyclesrefresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DCisolation Between power and control terminals insulation resistance > 1 MOhm 500 V DC for 1 minute to earth noise level 76 dB conforming to 86/188/EEC power dissipation in W 2026 W(forced convection) at 380 V, switching frequency 2.5 kHz operating position Vertical +/- 10 degree electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6pollution degree 2 conforming to EN/IEC 61800-5-1 vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6shock resistance 6 gn for 11 ms conforming to IEC 60068-2-27 relative humidity 5…95 % without condensation conforming to IEC 60068-2-3 ambient air temperature for operation -15…45 °C (without derating)
45…60 °C (with derating factor)operating altitude <= 1000 m without derating
1000…4800 m with current derating 1 % per 100 menvironmental characteristic Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3
Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3standards EN/IEC 61800-3
Environment 2 category C3 EN/IEC 61800-3
EN/IEC 61800-5-1
IEC 60721-3marking CE Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Weight 96.344 kg Package 1 Height 47 cm Package 1 width 67 cm Package 1 Length 103 cm