بی متال اشنایدر

فیلترها

دسته‌بندی را انتخاب کنید

LR9D5367

Main
rangeTeSys
product nameTeSys LRD
TeSys Deca
product or component typeElectronic thermal overload relay
device short nameLR9D
relay applicationMotor protection
product compatibilityLC1D115
LC1D150
NSX circuit breaker
network typeAC
thermal overload classClass 10 conforming to IEC 60947-4-1
signalling functionAlarm
thermal protection adjustment range60…100 A
[Ui] rated insulation voltagePower circuit: 1000 V conforming to IEC 60947-4-1
Power circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Complementary
network frequency50…60 Hz
[Us] rated supply voltage24 V DC
supply voltage limits17…32 V
mounting supportUnder contactor
Rail
tripping threshold1.05 +/- 0.06 In alarm conforming to IEC 60947-4-1
1.12 +/- 0.06 In de-energisation conforming to IEC 60947-4-1
auxiliary contact composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for signalling circuit
[Ue] rated operational voltage690 V AC 0…400 Hz for power circuit conforming to IEC 60947-4-1
associated fuse rating4 A gG for signalling circuit
4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1
phase failure sensitivityTripping in 4 s +/- 20 % conforming to IEC 60947-4-1
control typeRed push-button: stop
Blue push-button: reset
temperature compensation-20…60 °C
switching capacity in mA0…150 mA
maximum voltage drop<2.5 V closed state
connections – terminalsPower circuit: bars
Control circuit: screw clamp terminals 1 cable(s) 0.5…1.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 0.5…1.5 mm² flexible without cable end
Alarm circuit: screw clamp terminals 1 cable(s) 0.5…1.5 mm² flexible without cable end
tightening torqueAlarm circuit: 0.45 N.m – on screw clamp terminals
Power circuit: 18 N.m – on bars M8
Control circuit: 1.2 N.m – on screw clamp terminals
height118 mm
width115 mm
depth125 mm
net weight0.885 kg
Environment
protective treatmentTH conforming to IEC 60068
IP degree of protectionIP20 conforming to IEC 60529
ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
ambient air temperature for storage-60…70 °C
operating altitude<= 2000 m without derating
mechanical robustnessVibrations: 2 Gn, 5…300 Hz conforming to IEC 60068-2-6
Shocks: 13 Gn for 11 ms conforming to IEC 60068-2-7
dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
standardsEN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
product certificationsUL
CSA
CCC
UKCA
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight922 g
Package 1 Height13 cm
Package 1 width15 cm
Package 1 Length16 cm
Unit Type of Package 2S04
Number of Units in Package 212
Package 2 Weight11.91 kg
Package 2 Height30 cm
Package 2 width40 cm
Package 2 Length60 cm

LR9D5369

Main
rangeTeSys
product nameTeSys LRD
TeSys Deca
product or component typeElectronic thermal overload relay
device short nameLR9D
relay applicationMotor protection
product compatibilityNSX circuit breaker
LC1D150
LC1D115
network typeAC
thermal overload classClass 10 conforming to IEC 60947-4-1
signalling functionAlarm
thermal protection adjustment range90…150 A
[Ui] rated insulation voltagePower circuit: 1000 V conforming to IEC 60947-4-1
Power circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Complementary
network frequency50…60 Hz
[Us] rated supply voltage24 V DC
supply voltage limits17…32 V
mounting supportUnder contactor
Rail
tripping threshold1.05 +/- 0.06 In alarm conforming to IEC 60947-4-1
1.12 +/- 0.06 In de-energisation conforming to IEC 60947-4-1
auxiliary contact composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for signalling circuit
[Ue] rated operational voltage690 V AC 0…400 Hz for power circuit conforming to IEC 60947-4-1
associated fuse rating4 A gG for signalling circuit
4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1
phase failure sensitivityTripping in 4 s +/- 20 % conforming to IEC 60947-4-1
control typeRed push-button: stop
Blue push-button: reset
temperature compensation-20…60 °C
switching capacity in mA0…150 mA
maximum voltage drop<2.5 V closed state
connections – terminalsPower circuit: bars
Control circuit: screw clamp terminals 1 cable(s) 0.5…1.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 0.5…1.5 mm² flexible without cable end
Alarm circuit: screw clamp terminals 1 cable(s) 0.5…1.5 mm² flexible without cable end
tightening torqueAlarm circuit: 0.45 N.m – on screw clamp terminals
Power circuit: 18 N.m – on bars M8
Control circuit: 1.2 N.m – on screw clamp terminals
height118 mm
width115 mm
depth125 mm
net weight0.885 kg
Environment
climatic withstandConforming to IACS E10
IP degree of protectionIP20 conforming to IEC 60529
ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
ambient air temperature for storage-60…70 °C
operating altitude<= 2000 m without derating
mechanical robustnessVibrations: 2 Gn, 5…300 Hz conforming to IEC 60068-2-6
Shocks: 13 Gn for 11 ms conforming to IEC 60068-2-7
dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
standardsEN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
product certificationsUL
CSA
CCC
UKCA
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight924.0 g
Package 1 Height15.0 cm
Package 1 width16.0 cm
Package 1 Length13.0 cm
Unit Type of Package 2S04
Number of Units in Package 212
Package 2 Weight11.88 kg
Package 2 Height30.0 cm
Package 2 width40.0 cm
Package 2 Length60.0 cm
Unit Type of Package 3P06
Number of Units in Package 348
Package 3 Weight56.804 kg
Package 3 Height77.0 cm
Package 3 width80.0 cm
Package 3 Length60.0 cm

LR9F5371

Main
rangeTeSys
product nameTeSys LRF
device short nameLR9F
product or component typeElectronic thermal overload relay
relay applicationMotor protection
product compatibilityLC1F185…LC1F265
network typeAC
thermal overload classClass 10 conforming to IEC 60947-4
thermal protection adjustment range132…220 A
Complementary
network frequency50/60 Hz
mounting supportDirect on contactor
Plate
tripping threshold1.12 +/- 0.06 In tripping conforming to IEC 60947-4-1
surge withstand4 kV conforming to IEC 61000-4-5
contacts type and composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for control circuit
[Ue] rated operational voltage1000 V AC 50/60 Hz for power circuit conforming to VDE 0110 group C
[Ui] rated insulation voltagePower circuit: 1000 V AC conforming to IEC 60947-4
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-1
phase failure sensitivityTripping in 4 s +/- 20 % conforming to IEC 60947-4-1
resetManual reset on front relay
control typeDial white full-load current adjustment
Test button red
Push-button red reset
Push-button stop
local signallingTrip indicator
temperature compensation-20…70 °C
current consumption<= 5 mA no-load
switching capacity for alarm0…150 mA
maximum voltage drop<2.5 V closed state
connections – terminalsControl circuit: screw clamp terminals 1 cable 0.75…2.5 mm² – cable stiffness: flexible – with cable end
Control circuit: screw clamp terminals 1 cable 0.75…2.5 mm² – cable stiffness: solid
Control circuit: screw clamp terminals 1 cable 0.75…4 mm² – cable stiffness: flexible – without cable end
Control circuit: screw clamp terminals 2 cable 1…1.5 mm² – cable stiffness: flexible – with cable end
Control circuit: screw clamp terminals 2 cable 1…2.5 mm² – cable stiffness: flexible – without cable end
Control circuit: screw clamp terminals 2 cable 1 mm² – cable stiffness: solid
Power circuit: lugs-ring terminals M10
tightening torqueControl circuit: 1.2 N.m on screw clamp terminals
Power circuit: 35 N.m on screw clamp terminals
height101 mm
width115 mm
depth123.5 mm
net weight0.95 kg
Environment
standardsIEC 60255-17
IEC 60947-4-1
IEC 60255-8
VDE 0660
EN 60947-4-1
product certificationsUL
CSA
UKCA
protective treatmentTH
IP degree of protectionIP20 conforming to IEC 60529
IP20 conforming to VDE 0106
ambient air temperature for operation-20…55 °C conforming to IEC 60255-8
ambient air temperature for storage-40…85 °C
operating altitude<= 2000 m without derating
fire resistance850 °C conforming to IEC 60695-2-1
mechanical robustnessShocks: 13 Gn for 11 ms conforming to IEC 60068-2-7
Vibrations 5…300 Hz: 2 Gn conforming to IEC 60068-2-6
dielectric strength6 kV 50 Hz conforming to IEC 255-5
electromagnetic compatibilityResistance to electrostatic discharge: 6 kV in indirect mode conforming to IEC 61000-4-2
Resistance to electrostatic discharge: 8 kV in air conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test: 10 V/m conforming to IEC 61000-4-3
Fast transients immunity test: 2 kV conforming to IEC 61000-4-4
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight1.035 kg
Package 1 Height15.0 cm
Package 1 width16.5 cm
Package 1 Length13.0 cm
Unit Type of Package 2S04
Number of Units in Package 211
Package 2 Weight12.03 kg
Package 2 Height30.0 cm
Package 2 width40.0 cm
Package 2 Length60.0 cm
Unit Type of Package 3P06
Number of Units in Package 344
Package 3 Weight59.048 kg
Package 3 Height77.0 cm
Package 3 width60.0 cm
Package 3 Length80.0 cm

LRD03

Main
rangeTeSys
TeSys Deca
product nameTeSys LRD
TeSys Deca
product or component typeDifferential thermal overload relay
device short nameLRD
relay applicationMotor protection
product compatibilityLC1D25
LC1D18
LC1D38
LC1D12
LC1D32
LC1D09
network typeAC
DC
thermal overload classClass 10A conforming to IEC 60947-4-1
thermal protection adjustment range0.25…0.4 A
[Ui] rated insulation voltagePower circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
Complementary
network frequency0…400 Hz
mounting supportPlate, with specific accessories
Rail, with specific accessories
Under contactor
tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
auxiliary contact composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for signalling circuit
permissible current3 A at 120 V AC-15 for signalling circuit
0.22 A at 125 V DC-13 for signalling circuit
[Ue] rated operational voltage690 V AC 0…400 Hz for power circuit conforming to IEC 60947-4-1
associated fuse rating4 A gG for signalling circuit
4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage6 kV
phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
control typeRed push-button: stop
Blue push-button: reset
temperature compensation-20…60 °C
connections – terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² solid without cable end
tightening torqueControl circuit: 1.7 N.m – on screw clamp terminals
Power circuit: 1.7 N.m – on screw clamp terminals
height66 mm
width45 mm
depth70 mm
net weight0.124 kg
Environment
protective treatmentTH conforming to IEC 60068
IP degree of protectionIP20 conforming to IEC 60529
ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
ambient air temperature for storage-60…70 °C
flame retardanceV1 conforming to UL 94
mechanical robustnessVibrations: 6 Gn conforming to IEC 60068-2-6
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
standardsEN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
EN 50495
product certificationsIEC
UL
CSA
CCC
EAC
BV
RINA
DNV-GL
LROS (Lloyds register of shipping)
ATEX INERIS
UKCA
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight138 g
Package 1 Height5 cm
Package 1 width7.8 cm
Package 1 Length9 cm
Unit Type of Package 2S02
Number of Units in Package 224
Package 2 Weight4 kg
Package 2 Height15 cm
Package 2 width30 cm
Package 2 Length40 cm
Unit Type of Package 3P06
Number of Units in Package 3384
Package 3 Weight67 kg
Package 3 Height80 cm
Package 3 width80 cm
Package 3 Length60 cm

LRD04

Main
rangeTeSys
TeSys Deca
product nameTeSys LRD
TeSys Deca
product or component typeDifferential thermal overload relay
device short nameLRD
relay applicationMotor protection
product compatibilityLC1D25
LC1D38
LC1D32
LC1D18
LC1D12
LC1D09
network typeAC
DC
thermal overload classClass 10A conforming to IEC 60947-4-1
thermal protection adjustment range0.4…0.63 A
[Ui] rated insulation voltagePower circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
Complementary
network frequency0…400 Hz
mounting supportPlate, with specific accessories
Rail, with specific accessories
Under contactor
tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
auxiliary contact composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for signalling circuit
permissible current3 A at 120 V AC-15 for signalling circuit
0.22 A at 125 V DC-13 for signalling circuit
[Ue] rated operational voltage690 V AC 0…400 Hz for power circuit conforming to IEC 60947-4-1
associated fuse rating4 A gG for signalling circuit
4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage6 kV
phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
control typeRed push-button: stop
Blue push-button: reset
temperature compensation-20…60 °C
connections – terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² solid without cable end
tightening torqueControl circuit: 1.7 N.m – on screw clamp terminals
Power circuit: 1.7 N.m – on screw clamp terminals
height66 mm
width45 mm
depth70 mm
net weight0.124 kg
Environment
protective treatmentTH conforming to IEC 60068
IP degree of protectionIP20 conforming to IEC 60529
ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
ambient air temperature for storage-60…70 °C
flame retardanceV1 conforming to UL 94
mechanical robustnessVibrations: 6 Gn conforming to IEC 60068-2-6
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
standardsEN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
EN 50495
product certificationsIEC
UL
CSA
CCC
EAC
BV
RINA
DNV-GL
LROS (Lloyds register of shipping)
ATEX INERIS
UKCA
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight137 g
Package 1 Height4.9 cm
Package 1 width7.7 cm
Package 1 Length8.8 cm
Unit Type of Package 2S02
Number of Units in Package 224
Package 2 Weight3.62 kg
Package 2 Height15 cm
Package 2 width30 cm
Package 2 Length40 cm
Unit Type of Package 3P06
Number of Units in Package 3384
Package 3 Weight69.924 kg
Package 3 Height77 cm
Package 3 width60 cm
Package 3 Length80 cm

LRD05

Main
rangeTeSys
TeSys Deca
product nameTeSys LRD
TeSys Deca
product or component typeDifferential thermal overload relay
device short nameLRD
relay applicationMotor protection
product compatibilityLC1D25
LC1D38
LC1D12
LC1D32
LC1D18
LC1D09
network typeAC
DC
thermal overload classClass 10A conforming to IEC 60947-4-1
thermal protection adjustment range0.63…1 A
[Ui] rated insulation voltagePower circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
Complementary
network frequency0…400 Hz
mounting supportPlate, with specific accessories
Rail, with specific accessories
Under contactor
tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
auxiliary contact composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for signalling circuit
permissible current3 A at 120 V AC-15 for signalling circuit
0.22 A at 125 V DC-13 for signalling circuit
[Ue] rated operational voltage690 V AC 0…400 Hz for power circuit conforming to IEC 60947-4-1
associated fuse rating4 A gG for signalling circuit
4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage6 kV
phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
control typeRed push-button: stop
Blue push-button: reset
temperature compensation-20…60 °C
connections – terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² solid without cable end
tightening torqueControl circuit: 1.7 N.m – on screw clamp terminals
Power circuit: 1.7 N.m – on screw clamp terminals
height66 mm
width45 mm
depth70 mm
net weight0.124 kg
Environment
protective treatmentTH conforming to IEC 60068
IP degree of protectionIP20 conforming to IEC 60529
ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
ambient air temperature for storage-60…70 °C
flame retardanceV1 conforming to UL 94
mechanical robustnessVibrations: 6 Gn conforming to IEC 60068-2-6
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
standardsEN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
EN 50495
product certificationsIEC
UL
CSA
CCC
EAC
BV
RINA
DNV-GL
LROS (Lloyds register of shipping)
ATEX INERIS
UKCA
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight137 g
Package 1 Height4.9 cm
Package 1 width7.7 cm
Package 1 Length8.8 cm
Unit Type of Package 2S02
Number of Units in Package 224
Package 2 Weight3.634 kg
Package 2 Height15 cm
Package 2 width30 cm
Package 2 Length40 cm
Unit Type of Package 3P06
Number of Units in Package 3384
Package 3 Weight68.388 kg
Package 3 Height80 cm
Package 3 width80 cm
Package 3 Length60 cm

LRD06

Main
rangeTeSys
TeSys Deca
product nameTeSys LRD
TeSys Deca
product or component typeDifferential thermal overload relay
device short nameLRD
relay applicationMotor protection
product compatibilityLC1D25
LC1D32
LC1D12
LC1D18
LC1D38
LC1D09
network typeDC
AC
thermal overload classClass 10A conforming to IEC 60947-4-1
thermal protection adjustment range1…1.6 A
[Ui] rated insulation voltagePower circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
Complementary
network frequency0…400 Hz
mounting supportPlate, with specific accessories
Rail, with specific accessories
Under contactor
tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
auxiliary contact composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for signalling circuit
permissible current3 A at 120 V AC-15 for signalling circuit
0.22 A at 125 V DC-13 for signalling circuit
[Ue] rated operational voltage690 V AC 0…400 Hz for power circuit conforming to IEC 60947-4-1
associated fuse rating4 A gG for signalling circuit
4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage6 kV
phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
control typeRed push-button: stop
Blue push-button: reset
temperature compensation-20…60 °C
connections – terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² solid without cable end
tightening torqueControl circuit: 1.7 N.m – on screw clamp terminals
Power circuit: 1.7 N.m – on screw clamp terminals
height66 mm
width45 mm
depth70 mm
net weight0.124 kg
Environment
protective treatmentTH conforming to IEC 60068
IP degree of protectionIP20 conforming to IEC 60529
ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
ambient air temperature for storage-60…70 °C
flame retardanceV1 conforming to UL 94
mechanical robustnessVibrations: 6 Gn conforming to IEC 60068-2-6
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
standardsEN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
EN 50495
product certificationsIEC
UL
CSA
CCC
EAC
BV
RINA
DNV-GL
LROS (Lloyds register of shipping)
ATEX INERIS
UKCA
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight141.9 g
Package 1 Height5.2 cm
Package 1 width7.8 cm
Package 1 Length8.8 cm
Unit Type of Package 2S02
Number of Units in Package 224
Package 2 Weight3.649 kg
Package 2 Height15 cm
Package 2 width30 cm
Package 2 Length40 cm
Unit Type of Package 3P06
Number of Units in Package 3384
Package 3 Weight68.388 kg
Package 3 Height77 cm
Package 3 width60 cm
Package 3 Length80 cm

LRD07

Main
rangeTeSys
TeSys Deca
product nameTeSys LRD
TeSys Deca
product or component typeDifferential thermal overload relay
device short nameLRD
relay applicationMotor protection
product compatibilityLC1D18
LC1D38
LC1D32
LC1D25
LC1D12
LC1D09
network typeDC
AC
thermal overload classClass 10A conforming to IEC 60947-4-1
thermal protection adjustment range1.6…2.5 A
[Ui] rated insulation voltagePower circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
Complementary
network frequency0…400 Hz
mounting supportPlate, with specific accessories
Rail, with specific accessories
Under contactor
tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
auxiliary contact composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for signalling circuit
permissible current3 A at 120 V AC-15 for signalling circuit
0.22 A at 125 V DC-13 for signalling circuit
[Ue] rated operational voltage690 V AC 0…400 Hz for power circuit conforming to IEC 60947-4-1
associated fuse rating4 A gG for signalling circuit
4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage6 kV
phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
control typeRed push-button: stop
Blue push-button: reset
temperature compensation-20…60 °C
connections – terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² solid without cable end
tightening torqueControl circuit: 1.7 N.m – on screw clamp terminals
Power circuit: 1.7 N.m – on screw clamp terminals
height66 mm
width45 mm
depth70 mm
net weight0.124 kg
Environment
protective treatmentTH conforming to IEC 60068
IP degree of protectionIP20 conforming to IEC 60529
ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
ambient air temperature for storage-60…70 °C
flame retardanceV1 conforming to UL 94
mechanical robustnessVibrations: 6 Gn conforming to IEC 60068-2-6
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
standardsEN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
EN 50495
product certificationsIEC
UL
CSA
CCC
EAC
BV
RINA
DNV-GL
LROS (Lloyds register of shipping)
ATEX INERIS
UKCA
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight138 g
Package 1 Height4.9 cm
Package 1 width7.7 cm
Package 1 Length8.8 cm
Unit Type of Package 2S02
Number of Units in Package 224
Package 2 Weight3.653 kg
Package 2 Height15 cm
Package 2 width30 cm
Package 2 Length40 cm
Unit Type of Package 3P06
Number of Units in Package 3384
Package 3 Weight72.827 kg
Package 3 Height77 cm
Package 3 width60 cm
Package 3 Length80 cm

LRD08

Main
rangeTeSys
TeSys Deca
product nameTeSys LRD
TeSys Deca
product or component typeDifferential thermal overload relay
device short nameLRD
relay applicationMotor protection
product compatibilityLC1D12
LC1D09
LC1D25
LC1D38
LC1D32
LC1D18
network typeAC
DC
thermal overload classClass 10A conforming to IEC 60947-4-1
thermal protection adjustment range2.5…4 A
[Ui] rated insulation voltagePower circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
Complementary
network frequency0…400 Hz
mounting supportPlate, with specific accessories
Rail, with specific accessories
Under contactor
tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
auxiliary contact composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for signalling circuit
permissible current3 A at 120 V AC-15 for signalling circuit
0.22 A at 125 V DC-13 for signalling circuit
[Ue] rated operational voltage690 V AC 0…400 Hz for power circuit conforming to IEC 60947-4-1
associated fuse rating4 A gG for signalling circuit
4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage6 kV
phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
control typeRed push-button: stop
Blue push-button: reset
temperature compensation-20…60 °C
connections – terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² solid without cable end
tightening torqueControl circuit: 1.7 N.m – on screw clamp terminals
Power circuit: 1.7 N.m – on screw clamp terminals
height66 mm
width45 mm
depth70 mm
net weight0.124 kg
Environment
protective treatmentTH conforming to IEC 60068
IP degree of protectionIP20 conforming to IEC 60529
ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
ambient air temperature for storage-60…70 °C
flame retardanceV1 conforming to UL 94
mechanical robustnessVibrations: 6 Gn conforming to IEC 60068-2-6
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
standardsEN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
EN 50495
product certificationsIEC
UL
CSA
CCC
EAC
BV
RINA
DNV-GL
LROS (Lloyds register of shipping)
ATEX INERIS
UKCA
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight140.9 g
Package 1 Height4.8 cm
Package 1 width7.8 cm
Package 1 Length8.9 cm
Unit Type of Package 2S02
Number of Units in Package 224
Package 2 Weight3.72 kg
Package 2 Height15 cm
Package 2 width30 cm
Package 2 Length40 cm
Unit Type of Package 3P06
Number of Units in Package 3384
Package 3 Weight71.076 kg
Package 3 Height77 cm
Package 3 width60 cm
Package 3 Length80 cm

LRD12

Main
rangeTeSys
TeSys Deca
product nameTeSys LRD
TeSys Deca
product or component typeDifferential thermal overload relay
device short nameLRD
relay applicationMotor protection
product compatibilityLC1D18
LC1D25
LC1D32
LC1D12
LC1D09
LC1D38
network typeDC
AC
thermal overload classClass 10A conforming to IEC 60947-4-1
thermal protection adjustment range5.5…8 A
[Ui] rated insulation voltagePower circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
Complementary
network frequency0…400 Hz
mounting supportPlate, with specific accessories
Rail, with specific accessories
Under contactor
tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
auxiliary contact composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for signalling circuit
permissible current1.5 A at 240 V AC-15 for signalling circuit
0.1 A at 250 V DC-13 for signalling circuit
[Ue] rated operational voltage690 V AC 0…400 Hz for power circuit conforming to IEC 60947-4-1
associated fuse rating4 A gG for signalling circuit
4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage6 kV
phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
control typeRed push-button: stop
Blue push-button: reset
temperature compensation-20…60 °C
connections – terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² solid
tightening torqueControl circuit: 1.7 N.m – on screw clamp terminals
Power circuit: 1.7 N.m – on screw clamp terminals
height66 mm
width45 mm
depth70 mm
net weight0.124 kg
Environment
protective treatmentTH conforming to IEC 60068
IP degree of protectionIP20 conforming to IEC 60529
ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
ambient air temperature for storage-60…70 °C
flame retardanceV1 conforming to UL 94
mechanical robustnessVibrations: 6 Gn conforming to IEC 60068-2-6
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
standardsEN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
EN 50495
product certificationsIEC
UL
CSA
CCC
EAC
BV
RINA
DNV-GL
LROS (Lloyds register of shipping)
ATEX INERIS
UKCA
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight146 g
Package 1 Height5 cm
Package 1 width7.7 cm
Package 1 Length9 cm
Unit Type of Package 2S02
Number of Units in Package 224
Package 2 Weight3.81 kg
Package 2 Height15 cm
Package 2 width30 cm
Package 2 Length40 cm
Unit Type of Package 3P06
Number of Units in Package 3384
Package 3 Weight69.54 kg
Package 3 Height80 cm
Package 3 width80 cm
Package 3 Length60 cm

LRD21

Main
rangeTeSys
TeSys Deca
product nameTeSys LRD
TeSys Deca
product or component typeDifferential thermal overload relay
device short nameLRD
relay applicationMotor protection
product compatibilityLC1D32
LC1D18
LC1D25
LC1D38
network typeAC
DC
thermal overload classClass 10A conforming to IEC 60947-4-1
thermal protection adjustment range12…18 A
[Ui] rated insulation voltagePower circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
Complementary
network frequency0…400 Hz
mounting supportPlate, with specific accessories
Rail, with specific accessories
Under contactor
tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
auxiliary contact composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for signalling circuit
permissible current1.5 A at 240 V AC-15 for signalling circuit
0.1 A at 250 V DC-13 for signalling circuit
[Ue] rated operational voltage690 V AC 0…400 Hz for power circuit conforming to IEC 60947-4-1
associated fuse rating4 A gG for signalling circuit
4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage6 kV
phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
control typeRed push-button: stop
Blue push-button: reset
temperature compensation-20…60 °C
connections – terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² solid
tightening torqueControl circuit: 1.7 N.m – on screw clamp terminals
Power circuit: 2.5 N.m – on screw clamp terminals
height66 mm
width45 mm
depth70 mm
net weight0.124 kg
Environment
protective treatmentTH conforming to IEC 60068
IP degree of protectionIP20 conforming to IEC 60529
ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
ambient air temperature for storage-60…70 °C
flame retardanceV1 conforming to UL 94
mechanical robustnessVibrations: 6 Gn conforming to IEC 60068-2-6
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
standardsEN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
EN 50495
product certificationsIEC
UL
CSA
CCC
EAC
BV
RINA
DNV-GL
LROS (Lloyds register of shipping)
ATEX INERIS
UKCA
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight147 g
Package 1 Height5 cm
Package 1 width7.8 cm
Package 1 Length8.8 cm
Unit Type of Package 2S02
Number of Units in Package 224
Package 2 Weight3.842 kg
Package 2 Height15 cm
Package 2 width30 cm
Package 2 Length40 cm
Unit Type of Package 3P06
Number of Units in Package 3384
Package 3 Weight72.228 kg
Package 3 Height77 cm
Package 3 width60 cm
Package 3 Length80 cm

LRD22

Main
rangeTeSys
TeSys Deca
product nameTeSys LRD
TeSys Deca
product or component typeDifferential thermal overload relay
device short nameLRD
relay applicationMotor protection
product compatibilityLC1D25
LC1D32
LC1D38
network typeDC
AC
thermal overload classClass 10A conforming to IEC 60947-4-1
thermal protection adjustment range16…24 A
[Ui] rated insulation voltagePower circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
Complementary
network frequency0…400 Hz
mounting supportPlate, with specific accessories
Rail, with specific accessories
Under contactor
tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
auxiliary contact composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for signalling circuit
permissible current1.5 A at 240 V AC-15 for signalling circuit
0.1 A at 250 V DC-13 for signalling circuit
[Ue] rated operational voltage690 V AC 0…400 Hz for power circuit conforming to IEC 60947-4-1
associated fuse rating4 A gG for signalling circuit
4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage6 kV
phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
control typeRed push-button: stop
Blue push-button: reset
temperature compensation-20…60 °C
connections – terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² solid
tightening torqueControl circuit: 1.7 N.m – on screw clamp terminals
Power circuit: 2.5 N.m – on screw clamp terminals
height66 mm
width45 mm
depth70 mm
net weight0.124 kg
Environment
protective treatmentTH conforming to IEC 60068
IP degree of protectionIP20 conforming to IEC 60529
ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
ambient air temperature for storage-60…70 °C
flame retardanceV1 conforming to UL 94
mechanical robustnessVibrations: 6 Gn conforming to IEC 60068-2-6
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
standardsEN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
EN 50495
product certificationsIEC
UL
CSA
CCC
EAC
BV
RINA
DNV-GL
LROS (Lloyds register of shipping)
ATEX INERIS
UKCA
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight140.9 g
Package 1 Height5 cm
Package 1 width7.6 cm
Package 1 Length8.8 cm
Unit Type of Package 2S02
Number of Units in Package 224
Package 2 Weight3.731 kg
Package 2 Height15 cm
Package 2 width30 cm
Package 2 Length40 cm
Unit Type of Package 3P06
Number of Units in Package 3384
Package 3 Weight74.924 kg
Package 3 Height80 cm
Package 3 width80 cm
Package 3 Length60 cm

فروشگاه
مقايسه
حساب من