A9R50425
Range Acti9 Product name Acti9 iID K Product or component type Residual current circuit breaker (RCCB) Device short name IID K Poles description 4P Neutral position Left [In] rated current 25 A Network type AC Earth-leakage sensitivity 30 mA Earth-leakage protection time delay Instantaneous Earth-leakage protection class Type AC Quality labels VDE Device location in system Outgoer Network frequency 50/60 Hz [Ue] rated operational voltage 380…415 V AC 50/60 Hz residual current tripping technology Voltage independent Rated breaking and making capacity Idm 500 A
Im 500 ARated conditional short-circuit current GL63: Inc 4.5 kA
K60: Inc 6 kA
C60: Inc 6 kA[Ui] rated insulation voltage 440 V AC 50/60 Hz [Uimp] rated impulse withstand voltage 4 kV Surge current 250 A Contact position indicator No Control type Toggle Mounting mode Clip-on Mounting support DIN rail 9 mm pitches 8 Height 85 mm Width 72 mm Depth 69 mm Net weight 0.37 kg Colour White Mechanical durability 5000 cycles Electrical durability AC-1: 2000 cycles Locking options description Padlocking device Connections – terminals Tunnel type terminals top or bottom 1…35 mm² rigid
Tunnel type terminals top or bottom 1…25 mm² flexible
Tunnel type terminals top or bottom 1…25 mm² flexible with ferruleWire stripping length 16 mm for top or bottom connection Tightening torque 3.5 N.m top or bottom Standards EN/IEC 61008-1
EN/IEC 61008-2-1IP degree of protection IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529Pollution degree 2 Electromagnetic compatibility 8/20 µs impulse withstand, 200 A conforming to EN/IEC 61008-1 Ambient air temperature for operation -5…60 °C Ambient air temperature for storage -40…85 °C Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 7.5 cm Package 1 Width 8.5 cm Package 1 Length 10 cm Package 1 Weight 357 g Unit Type of Package 2 S03 Number of Units in Package 2 27 Package 2 Height 30 cm Package 2 Width 30 cm Package 2 Length 40 cm Package 2 Weight 10.257 kg Unit Type of Package 3 P12 Number of Units in Package 3 216 Package 3 Height 50 cm Package 3 Width 80 cm Package 3 Length 120 cm Package 3 Weight 93.008 kg
A9R50440
Range Acti9 Product name Acti9 iID K Product or component type Residual current circuit breaker (RCCB) Device short name IID K Poles description 4P Neutral position Left [In] rated current 40 A Network type AC Earth-leakage sensitivity 30 mA Earth-leakage protection time delay Instantaneous Earth-leakage protection class Type AC Quality labels VDE Device location in system Outgoer Network frequency 50/60 Hz [Ue] rated operational voltage 380…415 V AC 50/60 Hz residual current tripping technology Voltage independent Rated breaking and making capacity Idm 500 A
Im 500 ARated conditional short-circuit current GL63: Inc 4.5 kA
K60: Inc 6 kA
C60: Inc 6 kA[Ui] rated insulation voltage 440 V AC 50/60 Hz [Uimp] rated impulse withstand voltage 4 kV Surge current 250 A Contact position indicator No Control type Toggle Mounting mode Clip-on Mounting support DIN rail 9 mm pitches 8 Height 85 mm Width 72 mm Depth 69 mm Net weight 0.37 kg Colour White Mechanical durability 5000 cycles Electrical durability AC-1: 2000 cycles Locking options description Padlocking device Connections – terminals Tunnel type terminals top or bottom 1…35 mm² rigid
Tunnel type terminals top or bottom 1…25 mm² flexible
Tunnel type terminals top or bottom 1…25 mm² flexible with ferruleWire stripping length 16 mm for top or bottom connection Tightening torque 3.5 N.m top or bottom Standards EN/IEC 61008-1
EN/IEC 61008-2-1IP degree of protection IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529Pollution degree 2 Electromagnetic compatibility 8/20 µs impulse withstand, 200 A conforming to EN/IEC 61008-1 Ambient air temperature for operation -5…60 °C Ambient air temperature for storage -40…85 °C Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 8 cm Package 1 Width 7.5 cm Package 1 Length 10 cm Package 1 Weight 351 g Unit Type of Package 2 S03 Number of Units in Package 2 27 Package 2 Height 30 cm Package 2 Width 30 cm Package 2 Length 40 cm Package 2 Weight 10.993 kg Unit Type of Package 3 P12 Number of Units in Package 3 216 Package 3 Height 75 cm Package 3 Width 60 cm Package 3 Length 80 cm Package 3 Weight 95.944 kg
A9R75225
Range Acti9 Product name Acti9 iID K Product or component type Residual current circuit breaker (RCCB) Device short name IID K Poles description 2P Neutral position Left [In] rated current 25 A Network type AC Earth-leakage sensitivity 300 mA Earth-leakage protection time delay Instantaneous Earth-leakage protection class Type AC Quality labels VDE Device location in system Outgoer Network frequency 50/60 Hz [Ue] rated operational voltage 220…240 V AC 50/60 Hz residual current tripping technology Voltage independent Rated breaking and making capacity Idm 500 A
Im 500 ARated conditional short-circuit current GL63: Inc 4.5 kA
K60: Inc 6 kA
C60: Inc 6 kA[Ui] rated insulation voltage 440 V AC 50/60 Hz [Uimp] rated impulse withstand voltage 4 kV Surge current 250 A Contact position indicator No Control type Toggle Mounting mode Clip-on Mounting support DIN rail 9 mm pitches 4 Height 85 mm Width 36 mm Depth 69 mm Net weight 0.21 kg Colour White Mechanical durability 5000 cycles Electrical durability AC-1: 2000 cycles Locking options description Padlocking device Connections – terminals Tunnel type terminals top or bottom 1…35 mm² rigid
Tunnel type terminals top or bottom 1…25 mm² flexible
Tunnel type terminals top or bottom 1…25 mm² flexible with ferruleWire stripping length 16 mm for top or bottom connection Tightening torque 3.5 N.m top or bottom Standards EN/IEC 61008-1
EN/IEC 61008-2-1IP degree of protection IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529Pollution degree 2 Electromagnetic compatibility 8/20 µs impulse withstand, 200 A conforming to EN/IEC 61008-1 Ambient air temperature for operation -5…60 °C Ambient air temperature for storage -40…85 °C Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 4.1 cm Package 1 Width 8.2 cm Package 1 Length 10 cm Package 1 Weight 202 g Unit Type of Package 2 BB1 Number of Units in Package 2 6 Package 2 Height 10.5 cm Package 2 Width 9.5 cm Package 2 Length 25.5 cm Package 2 Weight 1.307 kg Unit Type of Package 3 S03 Number of Units in Package 3 54 Package 3 Height 30 cm Package 3 Width 30 cm Package 3 Length 40 cm Package 3 Weight 12.409 kg
A9R75240
Range Acti9 Product name Acti9 iID K Product or component type Residual current circuit breaker (RCCB) Device short name IID K Poles description 2P Neutral position Left [In] rated current 40 A Network type AC Earth-leakage sensitivity 300 mA Earth-leakage protection time delay Instantaneous Earth-leakage protection class Type AC Device location in system Outgoer Network frequency 50/60 Hz [Ue] rated operational voltage 220…240 V AC 50/60 Hz residual current tripping technology Voltage independent Rated breaking and making capacity Idm 500 A
Im 500 ARated conditional short-circuit current GL63: Inc 4.5 kA
K60: Inc 6 kA
C60: Inc 6 kA[Ui] rated insulation voltage 440 V AC 50/60 Hz [Uimp] rated impulse withstand voltage 4 kV Surge current 250 A Contact position indicator No Control type Toggle Mounting mode Clip-on Mounting support DIN rail 9 mm pitches 4 Height 85 mm Width 36 mm Depth 69 mm Net weight 0.21 kg Colour White Mechanical durability 5000 cycles Electrical durability AC-1: 2000 cycles Locking options description Padlocking device Connections – terminals Tunnel type terminals top or bottom 1…35 mm² rigid
Tunnel type terminals top or bottom 1…25 mm² flexible
Tunnel type terminals top or bottom 1…25 mm² flexible with ferruleWire stripping length 16 mm for top or bottom connection Tightening torque 3.5 N.m top or bottom Standards EN/IEC 61008-1
EN/IEC 61008-2-1IP degree of protection IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529Pollution degree 2 Electromagnetic compatibility 8/20 µs impulse withstand, 200 A conforming to EN/IEC 61008-1 Ambient air temperature for operation -5…60 °C Ambient air temperature for storage -40…85 °C Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 8.5 cm Package 1 Width 4 cm Package 1 Length 10 cm Package 1 Weight 202 g Unit Type of Package 2 BB1 Number of Units in Package 2 6 Package 2 Height 10.5 cm Package 2 Width 9 cm Package 2 Length 25.5 cm Package 2 Weight 1.311 kg Unit Type of Package 3 S03 Number of Units in Package 3 54 Package 3 Height 30 cm Package 3 Width 30 cm Package 3 Length 40 cm Package 3 Weight 12.03 kg
A9R75425
Range Acti9 Product name Acti9 iID K Product or component type Residual current circuit breaker (RCCB) Device short name IID K Poles description 4P Neutral position Left [In] rated current 25 A Network type AC Earth-leakage sensitivity 300 mA Earth-leakage protection time delay Instantaneous Earth-leakage protection class Type AC Quality labels VDE Device location in system Outgoer Network frequency 50/60 Hz [Ue] rated operational voltage 380…415 V AC 50/60 Hz residual current tripping technology Voltage independent Rated breaking and making capacity Idm 500 A
Im 500 ARated conditional short-circuit current GL63: Inc 4.5 kA
K60: Inc 6 kA
C60: Inc 6 kA[Ui] rated insulation voltage 440 V AC 50/60 Hz [Uimp] rated impulse withstand voltage 4 kV Surge current 250 A Contact position indicator No Control type Toggle Mounting mode Clip-on Mounting support DIN rail 9 mm pitches 8 Height 85 mm Width 72 mm Depth 69 mm Net weight 0.37 kg Colour White Mechanical durability 5000 cycles Electrical durability AC-1: 2000 cycles Locking options description Padlocking device Connections – terminals Tunnel type terminals top or bottom 1…35 mm² rigid
Tunnel type terminals top or bottom 1…25 mm² flexible
Tunnel type terminals top or bottom 1…25 mm² flexible with ferruleWire stripping length 16 mm for top or bottom connection Tightening torque 3.5 N.m top or bottom Standards EN/IEC 61008-1
EN/IEC 61008-2-1IP degree of protection IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529Pollution degree 2 Electromagnetic compatibility 8/20 µs impulse withstand, 200 A conforming to EN/IEC 61008-1 Ambient air temperature for operation -5…60 °C Ambient air temperature for storage -40…85 °C Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 7.5 cm Package 1 Width 8.5 cm Package 1 Length 10 cm Package 1 Weight 352 g Unit Type of Package 2 BB1 Number of Units in Package 2 3 Package 2 Height 9 cm Package 2 Width 10.5 cm Package 2 Length 25.5 cm Package 2 Weight 1.152 kg Unit Type of Package 3 S03 Number of Units in Package 3 27 Package 3 Height 30 cm Package 3 Width 30 cm Package 3 Length 40 cm Package 3 Weight 11.028 kg
A9R75440
Range Acti9 Product name Acti9 iID K Product or component type Residual current circuit breaker (RCCB) Device short name IID K Poles description 4P Neutral position Left [In] rated current 40 A Network type AC Earth-leakage sensitivity 300 mA Earth-leakage protection time delay Instantaneous Earth-leakage protection class Type AC Quality labels VDE Device location in system Outgoer Network frequency 50/60 Hz [Ue] rated operational voltage 380…415 V AC 50/60 Hz residual current tripping technology Voltage independent Rated breaking and making capacity Idm 500 A
Im 500 ARated conditional short-circuit current GL63: Inc 4.5 kA
K60: Inc 6 kA
C60: Inc 6 kA[Ui] rated insulation voltage 440 V AC 50/60 Hz [Uimp] rated impulse withstand voltage 4 kV Surge current 250 A Contact position indicator No Control type Toggle Mounting mode Clip-on Mounting support DIN rail 9 mm pitches 8 Height 85 mm Width 72 mm Depth 69 mm Net weight 0.37 kg Colour White Mechanical durability 5000 cycles Electrical durability AC-1: 2000 cycles Locking options description Padlocking device Connections – terminals Tunnel type terminals top or bottom 1…35 mm² rigid
Tunnel type terminals top or bottom 1…25 mm² flexible
Tunnel type terminals top or bottom 1…25 mm² flexible with ferruleWire stripping length 16 mm for top or bottom connection Tightening torque 3.5 N.m top or bottom Standards EN/IEC 61008-1
EN/IEC 61008-2-1IP degree of protection IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529Pollution degree 2 Electromagnetic compatibility 8/20 µs impulse withstand, 200 A conforming to EN/IEC 61008-1 Ambient air temperature for operation -5…60 °C Ambient air temperature for storage -40…85 °C Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 7.5 cm Package 1 Width 8.2 cm Package 1 Length 10 cm Package 1 Weight 352 g Unit Type of Package 2 BB1 Number of Units in Package 2 3 Package 2 Height 9 cm Package 2 Width 10.7 cm Package 2 Length 25.5 cm Package 2 Weight 1.147 kg Unit Type of Package 3 S03 Number of Units in Package 3 27 Package 3 Height 30 cm Package 3 Width 30 cm Package 3 Length 40 cm Package 3 Weight 11.08 kg
M9R11225
Range Multi9 Product name Multi9 ID Product or component type Residual current circuit breaker (RCCB) Device short name ID Device application Distribution Poles description 2P Neutral position Left [In] rated current 25 A Network type AC Earth-leakage sensitivity 30 mA Earth-leakage protection time delay Instantaneous Earth-leakage protection class Type AC Network frequency 50 Hz [Ue] rated operational voltage 220…240 V AC 50 Hz residual current tripping technology Voltage independent Rated breaking and making capacity Idm 250 A conforming to EN/IEC 61008-1 Rated conditional short-circuit current Inc 10 kA [Ui] rated insulation voltage 440 V AC 50 Hz conforming to EN/IEC 61008-1 [Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 61008-1 Surge current 250 A Contact position indicator Yes Control type Toggle Local signalling ON, OFF, fault trip Mounting mode Clip-on Mounting support DIN rail 9 mm pitches 4 Height 81 mm Width 36 mm Depth 73 mm Net weight 0.23 kg Colour Grey Mechanical durability 20000 cycles Electrical durability 2000 cycles Locking options description Padlocking device Connections – terminals Tunnel type terminal (top or bottom) 1…35 mm² – rigid
Tunnel type terminal (top or bottom) 1…25 mm² – flexible
Tunnel type terminal (top or bottom) 3 cable(s) 16 mm² – rigid
Tunnel type terminal (top or bottom) 3 cable(s) 10 mm² – flexible
Tunnel type terminal (top or bottom) 1…25 mm² – flexible with ferruleWire stripping length 15 mm for top or bottom connection Tightening torque 3.5 N.m top or bottom Standards EN/IEC 61008-1 Product certifications CE IP degree of protection IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529Pollution degree 3 Electromagnetic compatibility 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1 Tropicalisation 2 conforming to IEC 60068-1 Relative humidity 95 % at 55 °C Ambient air temperature for operation -5…40 °C Ambient air temperature for storage -40…60 °C Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 4.0 cm Package 1 Width 8.5 cm Package 1 Length 8.7 cm Package 1 Weight 205 g Unit Type of Package 2 S03 Number of Units in Package 2 36 Package 2 Height 30.0 cm Package 2 Width 30.0 cm Package 2 Length 40.0 cm Package 2 Weight 7.821 kg Unit Type of Package 3 P12 Number of Units in Package 3 288 Package 3 Height 44.4 cm Package 3 Width 80 cm Package 3 Length 120 cm Package 3 Weight 74.568 kg
M9R11240
Range | Multi9 |
---|---|
Product name | Multi9 ID |
Product or component type | Residual current circuit breaker (RCCB) |
Device short name | ID |
Device application | Distribution |
Poles description | 2P |
Neutral position | Left |
[In] rated current | 40 A |
Network type | AC |
Earth-leakage sensitivity | 30 mA |
Earth-leakage protection time delay | Instantaneous |
Earth-leakage protection class | Type AC |
Network frequency | 50 Hz |
---|---|
[Ue] rated operational voltage | 220…240 V AC 50 Hz |
residual current tripping technology | Voltage independent |
Rated breaking and making capacity | Idm 400 A conforming to EN/IEC 61008-1 |
Rated conditional short-circuit current | Inc 10 kA |
[Ui] rated insulation voltage | 440 V AC 50 Hz conforming to EN/IEC 61008-1 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 61008-1 |
Surge current | 250 A |
Contact position indicator | Yes |
Control type | Toggle |
Local signalling | ON, OFF, fault trip |
Mounting mode | Clip-on |
Mounting support | DIN rail |
9 mm pitches | 4 |
Height | 81 mm |
Width | 36 mm |
Depth | 73 mm |
Net weight | 0.23 kg |
Colour | Grey |
Mechanical durability | 20000 cycles |
Electrical durability | 2000 cycles |
Locking options description | Padlocking device |
Connections – terminals | Tunnel type terminal (top or bottom) 1…35 mm² – rigid Tunnel type terminal (top or bottom) 1…25 mm² – flexible Tunnel type terminal (top or bottom) 3 cable(s) 16 mm² – rigid Tunnel type terminal (top or bottom) 3 cable(s) 10 mm² – flexible Tunnel type terminal (top or bottom) 1…25 mm² – flexible with ferrule |
Wire stripping length | 15 mm for top or bottom connection |
Tightening torque | 3.5 N.m top or bottom |
Standards | EN/IEC 61008-1 |
---|---|
Product certifications | CE |
IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
Pollution degree | 3 |
Electromagnetic compatibility | 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1 |
Tropicalisation | 2 conforming to IEC 60068-1 |
Relative humidity | 95 % at 55 °C |
Ambient air temperature for operation | -5…40 °C |
Ambient air temperature for storage | -40…60 °C |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 4.0 cm |
Package 1 Width | 8.5 cm |
Package 1 Length | 9.0 cm |
Package 1 Weight | 205 g |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 54 |
Package 2 Height | 30.0 cm |
Package 2 Width | 30.0 cm |
Package 2 Length | 40.0 cm |
Package 2 Weight | 11.511 kg |
Unit Type of Package 3 | P12 |
Number of Units in Package 3 | 432 |
Package 3 Height | 44.4 cm |
Package 3 Width | 80 cm |
Package 3 Length | 120 cm |