کلید هوایی اشنایدر

فیلترها

دسته‌بندی را انتخاب کنید

NT08H1-47210

Main
range of productMasterPact NT
product or component typeBasic frame
device short nameMasterPact NT08
circuit breaker nameMasterPact NT08H1
poles description3P
network typeAC
breaking capacity codeH1
suitability for isolationYes conforming to IEC 60947-2
utilisation categoryCategory B
Complementary
network frequency50/60 Hz
control typePush-button
mounting modeDrawout
[In] rated current800 A at 40 °C
[Ui] rated insulation voltage1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage12 kV conforming to IEC 60947-2
[Icm] rated short-circuit making capacity88 kA 220/415 V AC at 50/60 Hz
88 kA 440 V AC at 50/60 Hz
88 kA 525 V AC at 50/60 Hz
88 kA 690 V AC at 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
circuit breaker CT rating800 A
breaking capacity42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 220/415 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
protection typeWithout protection
mechanical durability12500 cycles without maintenance conforming to IEC 60947-2
electrical durability3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-3: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
connection pitch70 mm
[Icw] rated short-time withstand current24 kA 3 s conforming to IEC 60947-2
42 kA 0.5 s conforming to IEC 60947-2
42 kA 1 s conforming to IEC 60947-2
maximum breaking time25 ms
maximum closing response time50 ms
height322 mm
width288 mm
depth276.5 mm
Environment
standardsIEC 60947-2
product certificationsLCIE
ASEFA
pollution degree3 conforming to IEC 60664-1
ambient air temperature for operation-25…70 °C
ambient air temperature for storage-40…85 °C
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight23.068 kg
Package 1 Height25.0 cm
Package 1 width40.0 cm
Package 1 Length40.0 cm

NT10H1 – 47130

Main
range of productMasterPact NT
product or component typeBasic frame
device short nameMasterPact NT10
circuit breaker nameMasterPact NT10H1
poles description3P
network typeAC
breaking capacity codeH1
suitability for isolationYes conforming to IEC 60947-2
utilisation categoryCategory B
Complementary
network frequency50/60 Hz
control typePush-button
mounting modeFixed
[In] rated current1000 A at 40 °C
[Ui] rated insulation voltage1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage12 kV conforming to IEC 60947-2
[Icm] rated short-circuit making capacity88 kA 220/415 V AC at 50/60 Hz
88 kA 440 V AC at 50/60 Hz
88 kA 525 V AC at 50/60 Hz
88 kA 690 V AC at 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
circuit breaker CT rating1000 A
breaking capacity42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 220/415 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
protection typeWithout protection
mechanical durability12500 cycles without maintenance conforming to IEC 60947-2
electrical durability3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-3: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
connection pitch70 mm
[Icw] rated short-time withstand current24 kA 3 s conforming to IEC 60947-2
42 kA 0.5 s conforming to IEC 60947-2
42 kA 1 s conforming to IEC 60947-2
maximum breaking time25 ms
maximum closing response time50 ms
height301 mm
width276 mm
depth196 mm
Environment
standardsIEC 60947-2
product certificationsLCIE
ASEFA
pollution degree3 conforming to IEC 60664-1
ambient air temperature for operation-25…70 °C
ambient air temperature for storage-40…85 °C
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight21.506 kg
Package 1 Height25.0 cm
Package 1 width40.0 cm
Package 1 Length40.0 cm

NT12H1 – 47140

Main
range of productMasterPact NT
product or component typeBasic frame
device short nameMasterPact NT12
circuit breaker nameMasterPact NT12H1
poles description3P
network typeAC
breaking capacity codeH1
suitability for isolationYes conforming to IEC 60947-2
utilisation categoryCategory B
Complementary
network frequency50/60 Hz
control typePush-button
mounting modeFixed
[In] rated current1250 A at 40 °C
[Ui] rated insulation voltage1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage12 kV conforming to IEC 60947-2
[Icm] rated short-circuit making capacity88 kA 220/415 V AC at 50/60 Hz
88 kA 440 V AC at 50/60 Hz
88 kA 525 V AC at 50/60 Hz
88 kA 690 V AC at 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
circuit breaker CT rating1250 A
breaking capacity42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 220/415 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
protection typeWithout protection
mechanical durability12500 cycles without maintenance conforming to IEC 60947-2
electrical durability3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-3: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
connection pitch70 mm
[Icw] rated short-time withstand current24 kA 3 s conforming to IEC 60947-2
42 kA 0.5 s conforming to IEC 60947-2
42 kA 1 s conforming to IEC 60947-2
maximum breaking time25 ms
maximum closing response time50 ms
height301 mm
width276 mm
depth196 mm
Environment
standardsIEC 60947-2
product certificationsASEFA
LCIE
pollution degree3 conforming to IEC 60664-1
ambient air temperature for operation-25…70 °C
ambient air temperature for storage-40…85 °C
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight21.506 kg
Package 1 Height25.0 cm
Package 1 width40.0 cm
Package 1 Length40.0 cm

NW20H13PML2EHH—48287

Main
product lineMasterpact NW
Product or component typeBasic framework
Product groupMasterpact NW32
circuit breaker nameMasterpact NW32H1
Pole definition3P
Network typeHUNGRY
degree codeH1
suitability for insulationYes conforming to IEC 60947-2
usage categoryCategory B
Complement
Mains frequency50/60Hz
Control typeOn/off button
Mounting typeWith drawers
[In] rated current3200 A at 40 °C
[Ui] rated insulation voltage1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage12 kV conforming to IEC 60947-2
[Icm] rated short-circuit making capacity143 kA 525 V AC at 50/60 Hz
143 kA 690 V AC at 50/60 Hz
[Ue] rated operating voltage690 V AC 50/60 Hz conforming to IEC 60947-2
circuit breaker CT value3200 A
cutting capacity65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
Protection typeWithout protection
mechanical durability10000 cycles without maintenance conforming to IEC 60947-2
20000 cycles with maintenance conforming to IEC 60947-2
electrical enduranceAC-3: 6000 cycles 440/690 V AC 50/60 Hz maintenance free conforming to IEC 60947-2
2500 cycles 690 V AC 50/60 Hz maintenance free conforming to IEC 60947-2
5000 cycles 440 V AC 50/60 Hz maintenance without conforming to IEC 60947-2
AC-23A: 2500 cycles 690 V AC 50/60 Hz maintenance free conforming to IEC 60947-2
AC-23A: 5000 cycles 440 V AC 50/60 Hz maintenance free conforming to IEC 60947-2
connection range115mm
[Icw] rated short-time withstand current65 kA 1 s conforming to IEC 60947-2
65 kA 3 s conforming to IEC 60947-2
maximum cutting time25ms
Maximum shutdown response time70 ms
height439mm
Width441mm
depth394.5mm
Environment
standardsIEC 60947-2
Product certificatesASTA
degree of contamination4 conforming to IEC 60664-1
ambient air temperature for operation-25…70 °C
Storage ambient conditions-40…85 °C
Packaging units
Unit package type 1PCE
Number of units in the packageOne
Package weight (Lbs)51,236 kg
Package 1 Height30.5 cm
Package 1 width29.5cm
Package 1 Length37.5 cm

NW25H13PML2EHH – 48070

Main
range of productMasterpact NW
product or component typeBasic frame
device short nameMasterpact NW25
circuit breaker nameMasterpact NW25H1
poles description3P
network typeAC
breaking capacity codeH1
suitability for isolationYes conforming to IEC 60947-2
utilisation categoryCategory B
Complementary
network frequency50/60 Hz
control typePush-button
mounting modeFixed
[In] rated current2500 A at 40 °C
[Ui] rated insulation voltage1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage12 kV conforming to IEC 60947-2
[Icm] rated short-circuit making capacity143 kA 525 V AC at 50/60 Hz
143 kA 690 V AC at 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
circuit breaker CT rating2500 A
breaking capacity65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
protection typeWithout protection
mechanical durability10000 cycles without maintenance conforming to IEC 60947-2
20000 cycles with maintenance conforming to IEC 60947-2
electrical durabilityAC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
connection pitch115 mm
[Icw] rated short-time withstand current65 kA 1 s conforming to IEC 60947-2
65 kA 3 s conforming to IEC 60947-2
maximum breaking time25 ms
maximum closing response time70 ms
height352 mm
width422 mm
depth297 mm
Environment
standardsIEC 60947-2
product certificationsASTA
pollution degree4 conforming to IEC 60664-1
ambient air temperature for operation-25…70 °C
ambient air temperature for storage-40…85 °C

NW32H13PML2EHH-48312

Main
product lineMasterpact NW
Product or component typeBasic framework
Product groupMasterpact NW32
circuit breaker nameMasterpact NW32H1
Pole definition3P
Network typeHUNGRY
degree codeH1
suitability for insulationYes conforming to IEC 60947-2
usage categoryCategory B
Complement
Mains frequency50/60Hz
Control typeOn/off button
Mounting typeWith drawers
[In] rated current3200 A at 40 °C
[Ui] rated insulation voltage1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage12 kV conforming to IEC 60947-2
[Icm] rated short-circuit making capacity143 kA 525 V AC at 50/60 Hz
143 kA 690 V AC at 50/60 Hz
[Ue] rated operating voltage690 V AC 50/60 Hz conforming to IEC 60947-2
circuit breaker CT value3200 A
cutting capacity65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
Protection typeWithout protection
mechanical durability10000 cycles without maintenance conforming to IEC 60947-2
20000 cycles with maintenance conforming to IEC 60947-2
electrical enduranceAC-3: 6000 cycles 440/690 V AC 50/60 Hz maintenance free conforming to IEC 60947-2
2500 cycles 690 V AC 50/60 Hz maintenance free conforming to IEC 60947-2
5000 cycles 440 V AC 50/60 Hz maintenance without conforming to IEC 60947-2
AC-23A: 2500 cycles 690 V AC 50/60 Hz maintenance free conforming to IEC 60947-2
AC-23A: 5000 cycles 440 V AC 50/60 Hz maintenance free conforming to IEC 60947-2
connection range115mm
[Icw] rated short-time withstand current65 kA 1 s conforming to IEC 60947-2
65 kA 3 s conforming to IEC 60947-2
maximum cutting time25ms
Maximum shutdown response time70 ms
height439mm
Width441mm
depth394.5mm
Environment
standardsIEC 60947-2
Product certificatesASTA
degree of contamination4 conforming to IEC 60664-1
ambient air temperature for operation-25…70 °C
Storage ambient conditions-40…85 °C
Packaging units
Unit package type 1PCE
Number of units in the packageOne
Package weight (Lbs)51,236 kg
Package 1 Height30.5 cm
Package 1 width29.5cm
Package 1 Length37.5 cm

فروشگاه