NT08H1-47210
range of product MasterPact NT product or component type Basic frame device short name MasterPact NT08 circuit breaker name MasterPact NT08H1 poles description 3P network type AC breaking capacity code H1 suitability for isolation Yes conforming to IEC 60947-2 utilisation category Category B network frequency 50/60 Hz control type Push-button mounting mode Drawout [In] rated current 800 A at 40 °C [Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2 [Icm] rated short-circuit making capacity 88 kA 220/415 V AC at 50/60 Hz
88 kA 440 V AC at 50/60 Hz
88 kA 525 V AC at 50/60 Hz
88 kA 690 V AC at 50/60 Hz[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 circuit breaker CT rating 800 A breaking capacity 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 220/415 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2protection type Without protection mechanical durability 12500 cycles without maintenance conforming to IEC 60947-2 electrical durability 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-3: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2connection pitch 70 mm [Icw] rated short-time withstand current 24 kA 3 s conforming to IEC 60947-2
42 kA 0.5 s conforming to IEC 60947-2
42 kA 1 s conforming to IEC 60947-2maximum breaking time 25 ms maximum closing response time 50 ms height 322 mm width 288 mm depth 276.5 mm standards IEC 60947-2 product certifications LCIE
ASEFApollution degree 3 conforming to IEC 60664-1 ambient air temperature for operation -25…70 °C ambient air temperature for storage -40…85 °C Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Weight 23.068 kg Package 1 Height 25.0 cm Package 1 width 40.0 cm Package 1 Length 40.0 cm
NT10H1 – 47130
range of product MasterPact NT product or component type Basic frame device short name MasterPact NT10 circuit breaker name MasterPact NT10H1 poles description 3P network type AC breaking capacity code H1 suitability for isolation Yes conforming to IEC 60947-2 utilisation category Category B network frequency 50/60 Hz control type Push-button mounting mode Fixed [In] rated current 1000 A at 40 °C [Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2 [Icm] rated short-circuit making capacity 88 kA 220/415 V AC at 50/60 Hz
88 kA 440 V AC at 50/60 Hz
88 kA 525 V AC at 50/60 Hz
88 kA 690 V AC at 50/60 Hz[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 circuit breaker CT rating 1000 A breaking capacity 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 220/415 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2protection type Without protection mechanical durability 12500 cycles without maintenance conforming to IEC 60947-2 electrical durability 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-3: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2connection pitch 70 mm [Icw] rated short-time withstand current 24 kA 3 s conforming to IEC 60947-2
42 kA 0.5 s conforming to IEC 60947-2
42 kA 1 s conforming to IEC 60947-2maximum breaking time 25 ms maximum closing response time 50 ms height 301 mm width 276 mm depth 196 mm standards IEC 60947-2 product certifications LCIE
ASEFApollution degree 3 conforming to IEC 60664-1 ambient air temperature for operation -25…70 °C ambient air temperature for storage -40…85 °C Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Weight 21.506 kg Package 1 Height 25.0 cm Package 1 width 40.0 cm Package 1 Length 40.0 cm
NT12H1 – 47140
range of product MasterPact NT product or component type Basic frame device short name MasterPact NT12 circuit breaker name MasterPact NT12H1 poles description 3P network type AC breaking capacity code H1 suitability for isolation Yes conforming to IEC 60947-2 utilisation category Category B network frequency 50/60 Hz control type Push-button mounting mode Fixed [In] rated current 1250 A at 40 °C [Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2 [Icm] rated short-circuit making capacity 88 kA 220/415 V AC at 50/60 Hz
88 kA 440 V AC at 50/60 Hz
88 kA 525 V AC at 50/60 Hz
88 kA 690 V AC at 50/60 Hz[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 circuit breaker CT rating 1250 A breaking capacity 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 220/415 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2protection type Without protection mechanical durability 12500 cycles without maintenance conforming to IEC 60947-2 electrical durability 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-3: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2connection pitch 70 mm [Icw] rated short-time withstand current 24 kA 3 s conforming to IEC 60947-2
42 kA 0.5 s conforming to IEC 60947-2
42 kA 1 s conforming to IEC 60947-2maximum breaking time 25 ms maximum closing response time 50 ms height 301 mm width 276 mm depth 196 mm standards IEC 60947-2 product certifications ASEFA
LCIEpollution degree 3 conforming to IEC 60664-1 ambient air temperature for operation -25…70 °C ambient air temperature for storage -40…85 °C Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Weight 21.506 kg Package 1 Height 25.0 cm Package 1 width 40.0 cm Package 1 Length 40.0 cm
NW20H13PML2EHH—48287
product line Masterpact NW Product or component type Basic framework Product group Masterpact NW32 circuit breaker name Masterpact NW32H1 Pole definition 3P Network type HUNGRY degree code H1 suitability for insulation Yes conforming to IEC 60947-2 usage category Category B Mains frequency 50/60Hz Control type On/off button Mounting type With drawers [In] rated current 3200 A at 40 °C [Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2 [Icm] rated short-circuit making capacity 143 kA 525 V AC at 50/60 Hz
143 kA 690 V AC at 50/60 Hz[Ue] rated operating voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 circuit breaker CT value 3200 A cutting capacity 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2Protection type Without protection mechanical durability 10000 cycles without maintenance conforming to IEC 60947-2
20000 cycles with maintenance conforming to IEC 60947-2electrical endurance AC-3: 6000 cycles 440/690 V AC 50/60 Hz maintenance free conforming to IEC 60947-2
2500 cycles 690 V AC 50/60 Hz maintenance free conforming to IEC 60947-2
5000 cycles 440 V AC 50/60 Hz maintenance without conforming to IEC 60947-2
AC-23A: 2500 cycles 690 V AC 50/60 Hz maintenance free conforming to IEC 60947-2
AC-23A: 5000 cycles 440 V AC 50/60 Hz maintenance free conforming to IEC 60947-2connection range 115mm [Icw] rated short-time withstand current 65 kA 1 s conforming to IEC 60947-2
65 kA 3 s conforming to IEC 60947-2maximum cutting time 25ms Maximum shutdown response time 70 ms height 439mm Width 441mm depth 394.5mm standards IEC 60947-2 Product certificates ASTA degree of contamination 4 conforming to IEC 60664-1 ambient air temperature for operation -25…70 °C Storage ambient conditions -40…85 °C Unit package type 1 PCE Number of units in the package One Package weight (Lbs) 51,236 kg Package 1 Height 30.5 cm Package 1 width 29.5cm Package 1 Length 37.5 cm
NW25H13PML2EHH – 48070
range of product Masterpact NW product or component type Basic frame device short name Masterpact NW25 circuit breaker name Masterpact NW25H1 poles description 3P network type AC breaking capacity code H1 suitability for isolation Yes conforming to IEC 60947-2 utilisation category Category B network frequency 50/60 Hz control type Push-button mounting mode Fixed [In] rated current 2500 A at 40 °C [Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2 [Icm] rated short-circuit making capacity 143 kA 525 V AC at 50/60 Hz
143 kA 690 V AC at 50/60 Hz[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 circuit breaker CT rating 2500 A breaking capacity 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2protection type Without protection mechanical durability 10000 cycles without maintenance conforming to IEC 60947-2
20000 cycles with maintenance conforming to IEC 60947-2electrical durability AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2connection pitch 115 mm [Icw] rated short-time withstand current 65 kA 1 s conforming to IEC 60947-2
65 kA 3 s conforming to IEC 60947-2maximum breaking time 25 ms maximum closing response time 70 ms height 352 mm width 422 mm depth 297 mm standards IEC 60947-2 product certifications ASTA pollution degree 4 conforming to IEC 60664-1 ambient air temperature for operation -25…70 °C ambient air temperature for storage -40…85 °C
NW32H13PML2EHH-48312
product line Masterpact NW Product or component type Basic framework Product group Masterpact NW32 circuit breaker name Masterpact NW32H1 Pole definition 3P Network type HUNGRY degree code H1 suitability for insulation Yes conforming to IEC 60947-2 usage category Category B Mains frequency 50/60Hz Control type On/off button Mounting type With drawers [In] rated current 3200 A at 40 °C [Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2 [Icm] rated short-circuit making capacity 143 kA 525 V AC at 50/60 Hz
143 kA 690 V AC at 50/60 Hz[Ue] rated operating voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 circuit breaker CT value 3200 A cutting capacity 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2Protection type Without protection mechanical durability 10000 cycles without maintenance conforming to IEC 60947-2
20000 cycles with maintenance conforming to IEC 60947-2electrical endurance AC-3: 6000 cycles 440/690 V AC 50/60 Hz maintenance free conforming to IEC 60947-2
2500 cycles 690 V AC 50/60 Hz maintenance free conforming to IEC 60947-2
5000 cycles 440 V AC 50/60 Hz maintenance without conforming to IEC 60947-2
AC-23A: 2500 cycles 690 V AC 50/60 Hz maintenance free conforming to IEC 60947-2
AC-23A: 5000 cycles 440 V AC 50/60 Hz maintenance free conforming to IEC 60947-2connection range 115mm [Icw] rated short-time withstand current 65 kA 1 s conforming to IEC 60947-2
65 kA 3 s conforming to IEC 60947-2maximum cutting time 25ms Maximum shutdown response time 70 ms height 439mm Width 441mm depth 394.5mm standards IEC 60947-2 Product certificates ASTA degree of contamination 4 conforming to IEC 60664-1 ambient air temperature for operation -25…70 °C Storage ambient conditions -40…85 °C Unit package type 1 PCE Number of units in the package One Package weight (Lbs) 51,236 kg Package 1 Height 30.5 cm Package 1 width 29.5cm Package 1 Length 37.5 cm