LADN04

Main
rangeTeSys
TeSys Deca
product nameTeSys D
TeSys Deca
product or component typeAuxiliary contact block
device short nameLADN
range compatibilityTeSys D LC1D
TeSys D CAD
TeSys F LC1F
TeSys F CR1F
TeSys Deca CAD
TeSys Deca LC1D
mounting locationFront
pole contact composition4 NC
Contacts operationInstantaneous
[Ue] rated operational voltage690 V AC 25…400 Hz
[Ie] rated operational current6 A at 120 V AC-15
1.04 A at 690 V AC-15
0.55 A at 125 V DC-13
0.1 A at 600 V DC-13
[Ui] rated insulation voltage690 V conforming to IEC 60947-5-1
600 V conforming to UL 60947-5-1
600 V conforming to CSA C22.2 No 60947-5-1
[Ith] conventional free air thermal current10 A (at 60 °C)
standardsEN/IEC 60947-5-1
UL 60947-5-1
CSA C22.2 No 60947-5-1
GB/T 14048.5
product certificationsIECEE CB Scheme
UL
CSA
CCC
EAC
UKCA
Complementary
Irms rated making capacity140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
permissible short-time rating100 A 60 °C 1 s
120 A 60 °C 500 ms
140 A 60 °C 100 ms
protection typeGG fuse 10 A
mechanical durability30 Mcycles
minimum switching current5 mA
minimum switching voltage17 V
non-overlap time1.5 ms on de-energisation no overlap between NC and NO contact
1.5 ms on energisation no overlap between NC and NO contact
insulation resistance> 10 MOhm
connections – terminalsScrew clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1…2.5 mm²rigid
Screw clamp terminals 2 cable(s) 1…2.5 mm²rigid
tightening torque1.7 N.m – with screwdriver flat Ø 6 mm
1.7 N.m – with screwdriver Philips No 2
colourDark grey
height48 mm
width44 mm
depth42 mm
net weight0.05 kg
Environment
environmental characteristicNormal environment
IP degree of protectionIP20 conforming to IEC 60529
protective treatmentTH conforming to IEC 60068
ambient air temperature for storage-60…80 °C
ambient air temperature for operation-5…60 °C
operating altitude3000 m

LADN11

Main
rangeTeSys
TeSys Deca
product nameTeSys D
TeSys Deca
product or component typeAuxiliary contact block
device short nameLADN
range compatibilityTeSys D CAD
TeSys D LC1D
TeSys F LC1F
TeSys F CR1F
TeSys Deca CAD
TeSys Deca LC1D
mounting locationFront
pole contact composition1 NO + 1 NC
Contacts operationInstantaneous
[Ue] rated operational voltage690 V AC 25…400 Hz
[Ie] rated operational current6 A at 120 V AC-15
1.04 A at 690 V AC-15
0.55 A at 125 V DC-13
0.1 A at 600 V DC-13
[Ui] rated insulation voltage690 V conforming to IEC 60947-5-1
600 V conforming to UL 60947-5-1
600 V conforming to CSA C22.2 No 60947-5-1
[Ith] conventional free air thermal current10 A (at 60 °C)
standardsEN/IEC 60947-5-1
UL 60947-5-1
CSA C22.2 No 60947-5-1
GB/T 14048.5
product certificationsIECEE CB Scheme
UL
CSA
CCC
EAC
UKCA
Complementary
Irms rated making capacity140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
permissible short-time rating100 A 60 °C 1 s
120 A 60 °C 500 ms
140 A 60 °C 100 ms
protection typeGG fuse 10 A
mechanical durability30 Mcycles
minimum switching current5 mA
minimum switching voltage17 V
non-overlap time1.5 ms on de-energisation no overlap between NC and NO contact
1.5 ms on energisation no overlap between NC and NO contact
insulation resistance> 10 MOhm
connections – terminalsScrew clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1…2.5 mm²rigid
Screw clamp terminals 2 cable(s) 1…2.5 mm²rigid
tightening torque1.7 N.m – with screwdriver flat Ø 6 mm
1.7 N.m – with screwdriver Philips No 2
colourDark grey
height48 mm
width26 mm
depth42 mm
Environment
environmental characteristicNormal environment
IP degree of protectionIP20 conforming to IEC 60529
protective treatmentTH conforming to IEC 60068
ambient air temperature for storage-60…80 °C
ambient air temperature for operation-5…60 °C
operating altitude3000 m

LADN20

Main
rangeTeSys
TeSys Deca
product nameTeSys D
TeSys Deca
product or component typeAuxiliary contact block
device short nameLADN
range compatibilityTeSys D CAD
TeSys D LC1D
TeSys F LC1F
TeSys F CR1F
TeSys Deca CAD
TeSys Deca LC1D
mounting locationFront
pole contact composition2 NO
Contacts operationInstantaneous
[Ue] rated operational voltage690 V AC 25…400 Hz
[Ui] rated insulation voltage690 V conforming to IEC 60947-5-1
600 V conforming to UL
600 V conforming to CSA
[Ith] conventional free air thermal current10 A (at 60 °C)
standardsUL 60947-5-1
CSA C22.2 No 60947-5-1
GB/T 14048.5
EN 50012
product certificationsCB
UL
CSA
CCC
EAC
UKCA
Complementary
Irms rated making capacity140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
permissible short-time rating100 A 60 °C 1 s
120 A 60 °C 500 ms
140 A 60 °C 100 ms
protection typeGG fuse 10 A
mechanical durability30 Mcycles
minimum switching current5 mA
minimum switching voltage17 V
non-overlap time1.5 ms on de-energisation no overlap between NC and NO contact
1.5 ms on energisation no overlap between NC and NO contact
insulation resistance> 10 MOhm
connections – terminalsScrew clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1…4 mm²rigid without cable end
Screw clamp terminals 2 cable(s) 1…4 mm²rigid without cable end
tightening torque1.7 N.m – with screwdriver flat Ø 6 mm
1.7 N.m – with screwdriver Philips No 2
1.7 N.m – with screwdriver pozidriv No 2
colourDark grey
height48 mm
width26 mm
depth42 mm
Environment
environmental characteristicNormal environment
IP degree of protectionIP20 conforming to IEC 60529
protective treatmentTH conforming to IEC 60068
ambient air temperature for storage-60…80 °C
ambient air temperature for operation-5…60 °C
operating altitude3000 m

LADN22

Main
rangeTeSys
TeSys Deca
product nameTeSys D
TeSys Deca
product or component typeAuxiliary contact block
device short nameLADN
range compatibilityTeSys D CAD
TeSys D LC1D
TeSys F LC1F
TeSys F CR1F
TeSys Deca CAD
TeSys Deca LC1D
mounting locationFront
pole contact composition2 NO + 2 NC
Contacts operationInstantaneous
[Ue] rated operational voltage690 V AC 25…400 Hz
[Ie] rated operational current6 A at 120 V AC-15
1.04 A at 690 V AC-15
0.55 A at 125 V DC-13
0.1 A at 600 V DC-13
[Ui] rated insulation voltage690 V conforming to IEC 60947-5-1
600 V conforming to UL 60947-5-1
600 V conforming to CSA C22.2 No 60947-5-1
[Ith] conventional free air thermal current10 A (at 60 °C)
standardsEN/IEC 60947-5-1
UL 60947-5-1
CSA C22.2 No 60947-5-1
GB/T 14048.5
product certificationsIECEE CB Scheme
UL
CSA
CCC
UKCA
Complementary
Irms rated making capacity140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
permissible short-time rating100 A 60 °C 1 s
120 A 60 °C 500 ms
140 A 60 °C 100 ms
protection typeGG fuse 10 A
mechanical durability30 Mcycles
minimum switching current5 mA
minimum switching voltage17 V
non-overlap time1.5 ms on de-energisation no overlap between NC and NO contact
1.5 ms on energisation no overlap between NC and NO contact
insulation resistance> 10 MOhm
connections – terminalsScrew clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1…2.5 mm²rigid
Screw clamp terminals 2 cable(s) 1…2.5 mm²rigid
tightening torque1.7 N.m – with screwdriver flat Ø 6 mm
1.7 N.m – with screwdriver Philips No 2
colourDark grey
height48 mm
width44 mm
depth42 mm
net weight0.05 kg
Environment
environmental characteristicNormal environment
IP degree of protectionIP20 conforming to IEC 60529
protective treatmentTH conforming to IEC 60068
ambient air temperature for storage-60…80 °C
ambient air temperature for operation-5…60 °C
operating altitude3000 m

LADN31

Main
rangeTeSys
TeSys Deca
product nameTeSys D
TeSys Deca
product or component typeAuxiliary contact block
device short nameLADN
range compatibilityTeSys D CAD
TeSys D LC1D
TeSys F LC1F
TeSys F CR1F
TeSys Deca CAD
TeSys Deca LC1D
mounting locationFront
pole contact composition3 NO + 1 NC
Contacts operationInstantaneous
[Ue] rated operational voltage690 V AC 25…400 Hz
[Ie] rated operational current6 A at 120 V AC-15
1.04 A at 690 V AC-15
0.55 A at 125 V DC-13
0.1 A at 600 V DC-13
[Ui] rated insulation voltage690 V conforming to IEC 60947-5-1
600 V conforming to UL 60947-5-1
600 V conforming to CSA C22.2 No 60947-5-1
[Ith] conventional free air thermal current10 A (at 60 °C)
standardsEN/IEC 60947-5-1
UL 60947-5-1
CSA C22.2 No 60947-5-1
GB/T 14048.5
product certificationsIECEE CB Scheme
UL
CSA
CCC
EAC
UKCA
Complementary
Irms rated making capacity140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
permissible short-time rating100 A 60 °C 1 s
120 A 60 °C 500 ms
140 A 60 °C 100 ms
protection typeGG fuse 10 A
mechanical durability30 Mcycles
minimum switching current5 mA
minimum switching voltage17 V
non-overlap time1.5 ms on de-energisation no overlap between NC and NO contact
1.5 ms on energisation no overlap between NC and NO contact
insulation resistance> 10 MOhm
connections – terminalsScrew clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1…2.5 mm²rigid
Screw clamp terminals 2 cable(s) 1…2.5 mm²rigid
tightening torque1.7 N.m – with screwdriver flat Ø 6 mm
1.7 N.m – with screwdriver Philips No 2
colourDark grey
height48 mm
width44 mm
depth42 mm
net weight0.05 kg
Environment
environmental characteristicNormal environment
IP degree of protectionIP20 conforming to IEC 60529
protective treatmentTH conforming to IEC 60068
ambient air temperature for storage-60…80 °C
ambient air temperature for operation-5…60 °C
operating altitude3000 m

LADN40

Main
rangeTeSys
TeSys Deca
product nameTeSys D
TeSys Deca
product or component typeAuxiliary contact block
device short nameLADN
range compatibilityTeSys D CAD
TeSys D LC1D
TeSys F LC1F
TeSys F CR1F
TeSys Deca CAD
TeSys Deca LC1D
mounting locationFront
pole contact composition4 NO
Contacts operationInstantaneous
[Ue] rated operational voltage690 V AC 25…400 Hz
[Ui] rated insulation voltage690 V conforming to IEC 60947-5-1
600 V conforming to UL
600 V conforming to CSA
[Ith] conventional free air thermal current10 A (at 60 °C)
standardsEN/IEC 60947-5-1
UL 60947-5-1
CSA C22.2 No 60947-5-1
GB/T 14048.5
EN 50012
product certificationsCB
UL
CSA
CCC
EAC
UKCA
Complementary
Irms rated making capacity140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
permissible short-time rating100 A 60 °C 1 s
120 A 60 °C 500 ms
140 A 60 °C 100 ms
protection typeGG fuse 10 A
mechanical durability30 Mcycles
minimum switching current5 mA
minimum switching voltage17 V
non-overlap time1.5 ms on de-energisation no overlap between NC and NO contact
1.5 ms on energisation no overlap between NC and NO contact
insulation resistance> 10 MOhm
connections – terminalsScrew clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1…4 mm²rigid without cable end
Screw clamp terminals 2 cable(s) 1…4 mm²rigid without cable end
tightening torque1.7 N.m – with screwdriver flat Ø 6 mm
1.7 N.m – with screwdriver Philips No 2
1.7 N.m – with screwdriver pozidriv No 2
colourDark grey
height48 mm
width44 mm
depth42 mm
net weight0.05 kg
Environment
environmental characteristicNormal environment
IP degree of protectionIP2x conforming to IEC 60529
protective treatmentTH conforming to IEC 60068
ambient air temperature for storage-60…80 °C
ambient air temperature for operation-5…60 °C
operating altitude3000 m
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight60.8 g
Package 1 Height4.2 cm
Package 1 width5 cm
Package 1 Length5 cm
Unit Type of Package 2P06
Number of Units in Package 21280
Package 2 Weight89.614 kg
Package 2 Height75 cm
Package 2 width80 cm
Package 2 Length60 cm
Unit Type of Package 3S03
Number of Units in Package 3160
Package 3 Weight10.202 kg
Package 3 Height30 cm
Package 3 width30 cm
Package 3 Length40 cm

LC1D09BD

Coil Voltage 24 V dc
Number of Poles 3
Contact Current Rating 9 A
Power Rating 4 kW
Normal State Configuration 3NO
Contact Voltage Rating 690 V ac
Series LC1D
Range TeSys D
Number Of Auxiliary Contacts 2
Terminal Type Screw
Width 45mm
Depth 93mm
Minimum Operating Temperature -5°C
Length 77mm
Maximum Operating Temperature +60°C

LC1D12M7

Main
rangeTeSys
TeSys Deca
product nameTeSys D
TeSys Deca
product or component typeContactor
device short nameLC1D
contactor applicationResistive load
Motor control
utilisation categoryAC-4
AC-1
AC-3
AC-3e
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: <= 690 V AC 25…400 Hz
Power circuit: <= 300 V DC
[Ie] rated operational current25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
12 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
motor power kW3 kW at 220…230 V AC 50/60 Hz (AC-3)
5.5 kW at 380…400 V AC 50/60 Hz (AC-3)
5.5 kW at 415…440 V AC 50/60 Hz (AC-3)
7.5 kW at 500 V AC 50/60 Hz (AC-3)
7.5 kW at 660…690 V AC 50/60 Hz (AC-3)
3.7 kW at 400 V AC 50/60 Hz (AC-4)
3 kW at 220…230 V AC 50/60 Hz (AC-3e)
5.5 kW at 380…400 V AC 50/60 Hz (AC-3e)
5.5 kW at 415…440 V AC 50/60 Hz (AC-3e)
7.5 kW at 500 V AC 50/60 Hz (AC-3e)
7.5 kW at 660…690 V AC 50/60 Hz (AC-3e)
motor power HP (UL / CSA)0.5 hp at 115 V AC 50/60 Hz for 1 phase motors
2 hp at 230/240 V AC 50/60 Hz for 1 phase motors
3 hp at 200/208 V AC 50/60 Hz for 3 phases motors
3 hp at 230/240 V AC 50/60 Hz for 3 phases motors
7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
10 hp at 575/600 V AC 50/60 Hz for 3 phases motors
control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage220 V AC 50/60 Hz
auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
overvoltage categoryIII
[Ith] conventional free air thermal current25 A (at 60 °C) for power circuit
10 A (at 60 °C) for signalling circuit
Irms rated making capacity250 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
rated breaking capacity250 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current105 A 40 °C – 10 s for power circuit
210 A 40 °C – 1 s for power circuit
30 A 40 °C – 10 min for power circuit
61 A 40 °C – 1 min for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit
associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1
40 A gG at <= 690 V coordination type 1 for power circuit
25 A gG at <= 690 V coordination type 2 for power circuit
average impedance2.5 mOhm – Ith 25 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
electrical durability2 Mcycles 12 A AC-3 at Ue <= 440 V
0.8 Mcycles 25 A AC-1 at Ue <= 440 V
2 Mcycles 12 A AC-3e at Ue <= 440 V
power dissipation per pole0.36 W AC-3
1.56 W AC-1
0.36 W AC-3e
Front coverWith
mounting supportRail
Plate
standardsCSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1
product certificationsBV
GOST
CSA
RINA
LROS (Lloyds register of shipping)
DNV
UL
GL
CCC
UKCA
connections – terminalsPower circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
tightening torquePower circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Power circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver pozidriv No 2
Power circuit: 2.5 N.m – on screw clamp terminals – with screwdriver pozidriv No 2
operating time12…22 ms closing
4…19 ms opening
safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability15 Mcycles
maximum operating rate3600 cyc/h 60 °C
Complementary
coil technologyWithout built-in suppressor module
control circuit voltage limits0.3…0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8…1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85…1.1 Uc (-40…60 °C):operational AC 60 Hz
1…1.1 Uc (60…70 °C):operational AC 50/60 Hz
inrush power in VA70 VA 60 Hz cos phi 0.75 (at 20 °C)
70 VA 50 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
7 VA 50 Hz cos phi 0.3 (at 20 °C)
heat dissipation2…3 W at 50/60 Hz
auxiliary contacts typeType mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency25…400 Hz
minimum switching current5 mA for signalling circuit
minimum switching voltage17 V for signalling circuit
non-overlap time1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance> 10 MOhm for signalling circuit
Environment
IP degree of protectionIP20 front face conforming to IEC 60529
protective treatmentTH conforming to IEC 60068-2-30
pollution degree3
ambient air temperature for operation-40…60 °C
60…70 °C with derating
ambient air temperature for storage-60…80 °C
operating altitude0…3000 m
fire resistance850 °C conforming to IEC 60695-2-1
mechanical robustnessVibrations contactor open: 2 Gn, 5…300 Hz
Vibrations contactor closed: 4 Gn, 5…300 Hz
Shocks contactor open: 10 Gn for 11 ms
Shocks contactor closed: 15 Gn for 11 ms
height77 mm
width45 mm
depth86 mm
net weight0.325 kg

LC1D18BD

Coil Voltage 24 V dc
Number of Poles 3
Contact Current Rating 18 A
Power Rating 7.5 kW
Normal State Configuration 3NO
Contact Voltage Rating 690 V ac
Series LC1D
Range TeSys D
Number Of Auxiliary Contacts 2
Terminal Type Screw
Width 45mm
Depth 93mm
Maximum Operating Temperature +60°C
Minimum Operating Temperature -5°C
Length 77mm

LC1D25BD

Coil Voltage 24 V dc
Number of Poles 3
Contact Current Rating 25 A
Power Rating 11 kW
Normal State Configuration 3NO
Contact Voltage Rating 690 V ac
Series LC1D
Range TeSys D
Number Of Auxiliary Contacts 2
Terminal Type Screw
Width 45mm
Depth 99mm
Maximum Operating Temperature +60°C
Length 85mm
Minimum Operating Temperature -40°C

LC1D65AM7

Main
rangeTeSys
TeSys Deca
product nameTeSys D
TeSys Deca
product or component typeContactor
device short nameLC1D
contactor applicationMotor control
Resistive load
utilisation categoryAC-4
AC-1
AC-3
AC-3e
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: <= 690 V AC 25…400 Hz
Power circuit: <= 300 V DC
[Ie] rated operational current80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
65 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
motor power kW11 kW at 400 V AC 50/60 Hz (AC-4)
18.5 kW at 220…230 V AC 50/60 Hz (AC-3)
30 kW at 380…400 V AC 50/60 Hz (AC-3)
37 kW at 500 V AC 50/60 Hz (AC-3)
37 kW at 660…690 V AC 50/60 Hz (AC-3)
18.5 kW at 220…230 V AC 50/60 Hz (AC-3e)
30 kW at 380…400 V AC 50/60 Hz (AC-3e)
37 kW at 500 V AC 50/60 Hz (AC-3e)
37 kW at 660…690 V AC 50/60 Hz (AC-3e)
motor power HP (UL / CSA)40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
5 hp at 115 V AC 50/60 Hz for 1 phase motors
10 hp at 230/240 V AC 50/60 Hz for 1 phase motors
20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
20 hp at 230/240 V AC 50/60 Hz for 3 phases motors
50 hp at 575/600 V AC 50/60 Hz for 3 phases motors
control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage220 V AC 50/60 Hz
auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
overvoltage categoryIII
[Ith] conventional free air thermal current10 A (at 60 °C) for signalling circuit
80 A (at 60 °C) for power circuit
Irms rated making capacity140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1000 A at 440 V for power circuit conforming to IEC 60947
rated breaking capacity1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current520 A 40 °C – 10 s for power circuit
900 A 40 °C – 1 s for power circuit
110 A 40 °C – 10 min for power circuit
260 A 40 °C – 1 min for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit
associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1
125 A gG at <= 690 V coordination type 1 for power circuit
125 A gG at <= 690 V coordination type 2 for power circuit
average impedance1.5 mOhm – Ith 80 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1
electrical durability1.4 Mcycles 80 A AC-1 at Ue <= 440 V
1.45 Mcycles 65 A AC-3 at Ue <= 440 V
1.45 Mcycles 65 A AC-3e at Ue <= 440 V
power dissipation per pole9.6 W AC-1
6.3 W AC-3
6.3 W AC-3e
Front coverWith
mounting supportRail
Plate
standardsCSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1
product certificationsUL
CCC
GOST
CSA
connections – terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²flexible without cable end
Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²flexible without cable end
Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²flexible with cable end
Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²flexible with cable end
Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²solid without cable end
Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²solid without cable end
tightening torqueControl circuit: 1.7 N.m – on EverLink BTR screw connectors – with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m – on EverLink BTR screw connectors – with screwdriver Philips No 2
Power circuit: 8 N.m – on EverLink BTR screw connectors – cable 25…35 mm² hexagonal screw head 4 mm
Power circuit: 5 N.m – on EverLink BTR screw connectors – cable 1…25 mm² hexagonal screw head 4 mm
Control circuit: 1.7 N.m – on EverLink BTR screw connectors – with screwdriver pozidriv No 2
Power circuit: 2.5 N.m – on EverLink BTR screw connectors – with screwdriver pozidriv No 2
– on EverLink BTR screw connectors
operating time4…19 ms opening
12…26 ms closing
safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability6 Mcycles
maximum operating rate3600 cyc/h 60 °C
Complementary
coil technologyWithout built-in suppressor module
control circuit voltage limits0.3…0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8…1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85…1.1 Uc (-40…60 °C):operational AC 60 Hz
1…1.1 Uc (60…70 °C):operational AC 50/60 Hz
inrush power in VA140 VA 60 Hz cos phi 0.75 (at 20 °C)
160 VA 50 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA13 VA 60 Hz cos phi 0.3 (at 20 °C)
15 VA 50 Hz cos phi 0.3 (at 20 °C)
heat dissipation4…5 W at 50/60 Hz
auxiliary contacts typeType mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency25…400 Hz
minimum switching current5 mA for signalling circuit
minimum switching voltage17 V for signalling circuit
non-overlap time1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance> 10 MOhm for signalling circuit
Environment
IP degree of protectionIP20 front face conforming to IEC 60529
climatic withstandConforming to IACS E10
conforming to IEC 60947-1 Annex Q category D
protective treatmentTH conforming to IEC 60068-2-30
pollution degree3
ambient air temperature for operation-40…60 °C
60…70 °C with derating
ambient air temperature for storage-60…80 °C
operating altitude0…3000 m
fire resistance850 °C conforming to IEC 60695-2-1
mechanical robustnessVibrations contactor open: 2 Gn, 5…300 Hz
Vibrations contactor closed: 4 Gn, 5…300 Hz
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 10 Gn for 11 ms
height122 mm
width55 mm
depth120 mm
net weight0.86 kg

LC1D80AM7

oil Voltage 220 V ac
Number of Poles 3
Contact Current Rating 66 A
Power Rating 37 kW
Normal State Configuration 1NC + 1NO
Range TeSys
Function Reversing

LC1D95M5

Main
rangeTeSys
product nameTeSys D
TeSys Deca
product or component typeContactor
device short nameLC1D
contactor applicationResistive load
Motor control
utilisation categoryAC-1
AC-4
AC-3
AC-3e
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: 1000 V AC 25…400 Hz
[Ie] rated operational current95 A (at <60 °C) at <= 440 V AC-3 for power circuit
125 A (at <60 °C) at <= 690 V AC-1 for power circuit
95 A (at <60 °C) at <= 440 V AC-3e for power circuit
motor power kW25 kW at 220…230 V AC 50 Hz (AC-3)
45 kW at 380…400 V AC 50 Hz (AC-3)
45 kW at 415…440 V AC 50 Hz (AC-3)
55 kW at 500 V AC 50 Hz (AC-3)
45 kW at 660…690 V AC 50 Hz (AC-3)
45 kW at 1000 V AC 50 Hz (AC-3)
motor power HP (UL / CSA)7.5 hp at 120 V AC 60 Hz for 1 phase motors
15 hp at 230/240 V AC 60 Hz for 1 phase motors
30 hp at 200/208 V AC 60 Hz for 3 phases motors
30 hp at 230/240 V AC 60 Hz for 3 phases motors
60 hp at 460/480 V AC 60 Hz for 3 phases motors
60 hp at 575/600 V AC 60 Hz for 3 phases motors
control circuit typeAC at 50 Hz
[Uc] control circuit voltage220 V AC 50 Hz
auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947
overvoltage categoryIII
[Ith] conventional free air thermal current10 A (at 60 °C) for signalling circuit
125 A (at 60 °C) for power circuit
Irms rated making capacity1100 A at 440 V AC for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
rated breaking capacity1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current1100 A 40 °C – 1 s for power circuit
800 A 40 °C – 10 s for power circuit
400 A 40 °C – 1 min for power circuit
135 A 40 °C – 10 min for power circuit
140 A – 100 ms for signalling circuit
120 A – 500 ms for signalling circuit
100 A – 1 s for signalling circuit
associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1
200 A gG at <= 690 V coordination type 1 for power circuit
160 A gG at <= 690 V coordination type 2 for power circuit
average impedance0.8 mOhm – Ith 125 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit: 1000 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
electrical durability1.2 Mcycles 95 A AC-3
1.3 Mcycles 125 A AC-1
1.2 Mcycles 95 A AC-3e
power dissipation per pole12.5 W AC-1
7.2 W AC-3
7.2 W AC-3e
Front coverWith
mounting supportPlate
Rail
standardsEN/IEC 60947-1
EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
product certificationsIECEE CB Scheme
UL
CSA
CCC
EAC
LROS (Lloyds register of shipping)
RINA
BV
DNV-GL
connections – terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: connector 1 cable(s) 4…50 mm²flexible without cable end
Power circuit: connector 2 cable(s) 4…25 mm²flexible without cable end
Power circuit: connector 1 cable(s) 4…50 mm²flexible with cable end
Power circuit: connector 2 cable(s) 4…16 mm²flexible with cable end
Power circuit: connector 1 cable(s) 4…50 mm²solid without cable end
Power circuit: connector 2 cable(s) 4…25 mm²solid without cable end
tightening torqueControl circuit: 1.2 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver Philips No 2
Power circuit: 12 N.m – on connector – with screwdriver flat Ø 6 to Ø 8 mm
Power circuit: 12 N.m – on connector hexagonal screw head 4 mm
Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver pozidriv No 2
operating time20…35 ms closing
6…20 ms opening
safety reliability levelB10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability10 Mcycles
maximum operating rate3600 cyc/h 60 °C
Complementary
coil technologyWithout built-in suppressor module
control circuit voltage limits0.3…0.6 Uc (-40…70 °C):drop-out AC 50 Hz
0.85…1.1 Uc (-40…55 °C):operational AC 50 Hz
1…1.1 Uc (55…70 °C):operational AC 50 Hz
inrush power in VA200 VA 50 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA20 VA 50 Hz cos phi 0.3 (at 20 °C)
heat dissipation6…10 W at 50 Hz
auxiliary contacts typeType mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency25…400 Hz
minimum switching current5 mA for signalling circuit
minimum switching voltage17 V for signalling circuit
non-overlap time1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance> 10 MOhm for signalling circuit
Environment
IP degree of protectionIP20 front face conforming to IEC 60529
climatic withstandConforming to IACS E10
protective treatmentTH conforming to IEC 60068-2-30
pollution degree3
ambient air temperature for operation-40…60 °C
60…70 °C with derating
ambient air temperature for storage-60…80 °C
operating altitude0…3000 m
fire resistance850 °C conforming to IEC 60695-2-1
mechanical robustnessVibrations contactor open: 2 Gn, 5…300 Hz
Shocks contactor open: 8 Gn for 11 ms
Vibrations contactor closed: 3 Gn, 5…300 Hz
Shocks contactor closed: 10 Gn for 11 ms
height127 mm
width85 mm
depth130 mm
net weight1.61 kg

LC1DFKM7

Main
rangeTeSys
TeSys Deca
product nameTeSys LC1D.K
TeSys Deca
product or component typeCapacitor duty contactor
device short nameLC1DFK
device applicationControl
contactor applicationPower factor correction
utilisation categoryAC-6b
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: 690 V AC 50/60 Hz
reactive power rating7 kvar at 230 V AC 50 Hz 60 °C
12.5 kvar at 400 V AC 50 Hz 60 °C
13 kvar at 440 V AC 50 Hz 60 °C
21 kvar at 690 V AC 50 Hz 60 °C
control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage220 V AC 50/60 Hz
auxiliary contact composition1 NO + 2 NC instantaneous
electrical durability300000 cycles at Ue 400 V
200000 cycles at Ue 690 V
mounting supportDIN rail
Plate
standardsEN/IEC 60947-1
EN/IEC 60947-4-1
IEC 60335-1
product certificationsIECEE CB Scheme
UKCA
connections – terminalsControl circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: solid
Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: solid
Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 1.5…6 mm² – cable stiffness: solid
Power circuit: screw clamp terminals 2 1.5…4 mm² – cable stiffness: solid
Power circuit: screw clamp terminals 1 1.5…6 mm² – cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 1.5…6 mm² – cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 1.5…6 mm² – cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 1.5…4 mm² – cable stiffness: flexible with cable end
tightening torqueControl circuit: 1.7 N.m – on screw clamp terminals
Power circuit: 1.7 N.m – on screw clamp terminals
maximum operating rate240 cyc/h
Complementary
auxiliary contacts typeType mechanically linked 1 NO + 2 NC conforming to IEC 60947-5-1
Environment
IP degree of protectionIP20 front face conforming to IEC 60529
ambient air temperature for operation-5…60 °C
ambient air temperature for storage-60…80 °C
operating altitude0…3000 m
height115 mm
width45 mm
depth121 mm
net weight0.53 kg

LC1DGKM7

Main
rangeTeSys
TeSys Deca
product nameTeSys LC1D.K
TeSys Deca
product or component typeCapacitor duty contactor
device short nameLC1DGK
device applicationControl
contactor applicationPower factor correction
utilisation categoryAC-6b
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: 690 V AC 50/60 Hz
reactive power rating9.5 kvar at 230 V AC 50 Hz 60 °C
16.7 kvar at 400 V AC 50 Hz 60 °C
18 kvar at 440 V AC 50 Hz 60 °C
28.5 kvar at 690 V AC 50 Hz 60 °C
control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage220 V AC 50/60 Hz
auxiliary contact composition1 NO + 2 NC instantaneous
electrical durability300000 cycles at Ue 400 V
200000 cycles at Ue 690 V
mounting supportDIN rail
Plate
standardsEN/IEC 60947-1
EN/IEC 60947-4-1
IEC 60335-1
product certificationsIECEE CB Scheme
UKCA
connections – terminalsControl circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: solid
Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: solid
Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 2.5…16 mm² – cable stiffness: solid
Power circuit: screw clamp terminals 2 2.5…6 mm² – cable stiffness: solid
Power circuit: screw clamp terminals 1 1.5…10 mm² – cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 1.5…6 mm² – cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 1…10 mm² – cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible with cable end
tightening torqueControl circuit: 1.7 N.m – on screw clamp terminals
Power circuit: 2.5 N.m – on screw clamp terminals
maximum operating rate240 cyc/h
Complementary
auxiliary contacts typeType mechanically linked 1 NO + 2 NC conforming to IEC 60947-5-1
Environment
IP degree of protectionIP20 front face conforming to IEC 60529
ambient air temperature for operation-5…60 °C
ambient air temperature for storage-60…80 °C
operating altitude0…3000 m
height125 mm
width45 mm
depth127 mm
net weight0.6 kg

LC1DMKM7

Main
rangeTeSys
TeSys Deca
product nameTeSys LC1D.K
TeSys Deca
product or component typeCapacitor duty contactor
device short nameLC1DMK
device applicationControl
contactor applicationPower factor correction
utilisation categoryAC-6b
poles description3P
power pole contact composition3 NO
device location in systemLine interruption
Inside delta interruption
[Ue] rated operational voltagePower circuit: 690 V AC 50/60 Hz
reactive power rating14 kvar at 230 V AC 50 Hz 60 °C
25 kvar at 400 V AC 50 Hz 60 °C
27 kvar at 440 V AC 50 Hz 60 °C
42 kvar at 690 V AC 50 Hz 60 °C
control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage220 V AC 50/60 Hz
auxiliary contact composition1 NO + 2 NC instantaneous
electrical durability300000 cycles at Ue 400 V
200000 cycles at Ue 690 V
mounting supportDIN rail
Plate
standardsEN/IEC 60947-1
EN/IEC 60947-4-1
IEC 60335-1
product certificationsIECEE CB Scheme
UKCA
connections – terminalsControl circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: solid
Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: solid
Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 2.5…16 mm² – cable stiffness: solid
Power circuit: screw clamp terminals 2 2.5…6 mm² – cable stiffness: solid
Power circuit: screw clamp terminals 1 1.5…10 mm² – cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 1.5…6 mm² – cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 1…10 mm² – cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible with cable end
tightening torqueControl circuit: 1.7 N.m – on screw clamp terminals
Power circuit: 2.5 N.m – on screw clamp terminals
maximum operating rate240 cyc/h
Complementary
auxiliary contacts typeType mechanically linked 1 NO + 2 NC conforming to IEC 60947-5-1
Environment
IP degree of protectionIP20 front face conforming to IEC 60529
ambient air temperature for operation-5…60 °C
ambient air temperature for storage-60…80 °C
operating altitude0…3000 m
height125 mm
width45 mm
depth127 mm
net weight0.63 kg

LC1DWK12M7

Main
rangeTeSys
product nameTeSys LC1D.K
product or component typeCapacitor duty contactor
device short nameLC1DWK
device applicationControl
contactor applicationPower factor correction
utilisation categoryAC-6b
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: 690 V AC 50/60 Hz
reactive power rating35 kvar at 230 V AC 50 Hz 60 °C
63 kvar at 400 V AC 50 Hz 60 °C
67 kvar at 440 V AC 50 Hz 60 °C
104 kvar at 690 V AC 50 Hz 60 °C
30 kvar at 230 V AC 60 Hz 60 °C
60 kvar at 460 V AC 60 Hz 60 °C
80 kvar at 575 V AC 60 Hz 60 °C
control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage220 V AC 50/60 Hz
auxiliary contact composition1 NO + 2 NC instantaneous
electrical durability300000 cycles at Ue 400 V
200000 cycles at Ue 690 V
mounting supportDIN rail
Plate
standardsEN/IEC 60947-1
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
product certificationsIECEE CB Scheme
UL
CSA
UKCA
connections – terminalsControl circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: solid
Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: solid
Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible with cable end
Power circuit: connector 1 4…50 mm² – cable stiffness: solid
Power circuit: connector 2 4…25 mm² – cable stiffness: solid
Power circuit: connector 1 4…50 mm² – cable stiffness: flexible without cable end
Power circuit: connector 2 4…25 mm² – cable stiffness: flexible without cable end
Power circuit: connector 1 4…50 mm² – cable stiffness: flexible with cable end
Power circuit: connector 2 4…16 mm² – cable stiffness: flexible with cable end
tightening torquePower circuit: 9 N.m – on connector
Control circuit: 1.7 N.m – on screw clamp terminals
maximum operating rate240 cyc/h
Complementary
auxiliary contacts typeType mechanically linked 1 NO + 2 NC conforming to IEC 60947-5-1
Environment
IP degree of protectionIP20 front face conforming to IEC 60529
ambient air temperature for operation-5…60 °C
ambient air temperature for storage-60…80 °C
operating altitude0…3000 m
height180 mm
width85 mm
depth154 mm
net weight1.65 kg
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight1.721 kg
Package 1 Height13 cm
Package 1 width17 cm
Package 1 Length19 cm
Unit Type of Package 2P06
Number of Units in Package 248
Package 2 Weight90.608 kg
Package 2 Height75 cm
Package 2 width80 cm
Package 2 Length60 cm

LC1F115M7

range of product Easy Altivar 610
product or component type Variable speed drive
product specific application Fan, pump, compressor, conveyor
device short name ATV610
variant Standard version
product destination Asynchronous motors
mounting mode Cabinet mount
EMC filter Integrated conforming to EN/IEC 61800-3 category C3 with 50 m
IP degree of protection IP20
type of cooling Forced convection
supply frequency 50…60 Hz +/-5 %
network number of phases 3 phases
[Us] rated supply voltage 380…460 V – 15…10 %
motor power kW 110 kW for normal duty 90 kW for heavy duty
motor power hp 150 hp for normal duty 125 hp for heavy duty
line current 201 A at 380 V (normal duty) 175.7 A at 460 V (normal duty) 170 A at 380 V (heavy duty) 149.1 A at 460 V (heavy duty)
prospective line Isc 50 kA
apparent power 140.0 kVA at 460 V (normal duty) 118.8 kVA at 460 V (heavy duty)
continuous output current 211 A at 2.5 kHz for normal duty 173 A at 2.5 kHz for heavy duty
maximum transient current 232 A during 60 s (normal duty) 260 A during 60 s (heavy duty)
asynchronous motor control profile Variable torque standard Optimized torque mode Constant torque standard
output frequency 0.0001…0.5 kHz
nominal switching frequency 2.5 kHz
switching frequency 1…8 kHz adjustable
number of preset speeds 16 preset speeds
communication port protocol Modbus serial
option card Slot A: communication card, Profibus DP V1 Slot A: digital or analog I/O extension card Slot A: relay output card
output voltage <= power supply voltage
motor slip compensation Can be suppressed Adjustable Not available in permanent magnet motor law Automatic whatever the load
acceleration and deceleration ramps Linear adjustable separately from 0.01 to 9000 s S, U or customized
braking to standstill By DC injection
protection type Thermal protection: motor Motor phase break: motor Thermal protection: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
frequency resolution Display unit: 0.1 Hz Analog input: 0.012/50 Hz
electrical connection Control, screw terminal: 0.5…1.5 mm² Line side, screw terminal: 2 x 50…3 x 120 mm² Motor, screw terminal: 3 x 50…3 x 120 mm²
connector type 1 RJ45 (on the remote graphic terminal) for Modbus serial
physical interface 2-wire RS 485 for Modbus serial
transmission frame RTU for Modbus serial
transmission rate 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
type of polarization No impedance for Modbus serial
number of addresses 1…247 for Modbus serial
method of access Slave
supply External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
local signalling 2 LEDs for local diagnostic 1 LED (yellow) for embedded communication status 2 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage
width 320 mm
height 852 mm 1159 mm with IP21 conformity kit
depth 390 mm
net weight 82 kg
analogue input number 3
analogue input type AI1, AI2, AI3 software-configurable voltage: 0…10 V DC, impedance: 30 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits AI2, AI3 software-configurable temperature probe or water level sensor
discrete input number 6
discrete input type DI1…DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
input compatibility DI1…DI6: logic input level 1 PLC conforming to EN/IEC 61131-2 DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68
discrete input logic Positive logic (source): DI1…DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1) Negative logic (sink): DI1…DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1) Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1)
analogue output number 2
analogue output type Software-configurable current AQ1, AQ2: 0…20 mA, resolution 10 bits Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bits
sampling duration 5 ms +/- 0.1 ms (AI1, AI2, AI3) – analog input 2 ms +/- 0.5 ms (DI1…DI6)configurable – discrete input 5 ms +/- 1 ms (DI5, DI6)configurable – pulse input 10 ms +/- 1 ms (AQ1, AQ2) – analog output
accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AQ1, AQ2: +/- 0.2 % for analog output
relay output number 3
relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC
maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
isolation Between power and control terminals
insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
noise level 76 dB conforming to 86/188/EEC
power dissipation in W 2026 W(forced convection) at 380 V, switching frequency 2.5 kHz
operating position Vertical +/- 10 degree
electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
pollution degree 2 conforming to EN/IEC 61800-5-1
vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
shock resistance 6 gn for 11 ms conforming to IEC 60068-2-27
relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
ambient air temperature for operation -15…45 °C (without derating) 45…60 °C (with derating factor)
operating altitude <= 1000 m without derating 1000…4800 m with current derating 1 % per 100 m
environmental characteristic Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3
standards EN/IEC 61800-3 Environment 2 category C3 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 60721-3
marking CE
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 96.344 kg
Package 1 Height 47 cm
Package 1 width 67 cm
Package 1 Length 103 cm

LC1F185M5

range of product Easy Altivar 610
product or component type Variable speed drive
product specific application Fan, pump, compressor, conveyor
device short name ATV610
variant Standard version
product destination Asynchronous motors
mounting mode Cabinet mount
EMC filter Integrated conforming to EN/IEC 61800-3 category C3 with 50 m
IP degree of protection IP20
type of cooling Forced convection
supply frequency 50…60 Hz +/-5 %
network number of phases 3 phases
[Us] rated supply voltage 380…460 V – 15…10 %
motor power kW 110 kW for normal duty 90 kW for heavy duty
motor power hp 150 hp for normal duty 125 hp for heavy duty
line current 201 A at 380 V (normal duty) 175.7 A at 460 V (normal duty) 170 A at 380 V (heavy duty) 149.1 A at 460 V (heavy duty)
prospective line Isc 50 kA
apparent power 140.0 kVA at 460 V (normal duty) 118.8 kVA at 460 V (heavy duty)
continuous output current 211 A at 2.5 kHz for normal duty 173 A at 2.5 kHz for heavy duty
maximum transient current 232 A during 60 s (normal duty) 260 A during 60 s (heavy duty)
asynchronous motor control profile Variable torque standard Optimized torque mode Constant torque standard
output frequency 0.0001…0.5 kHz
nominal switching frequency 2.5 kHz
switching frequency 1…8 kHz adjustable
number of preset speeds 16 preset speeds
communication port protocol Modbus serial
option card Slot A: communication card, Profibus DP V1 Slot A: digital or analog I/O extension card Slot A: relay output card
output voltage <= power supply voltage
motor slip compensation Can be suppressed Adjustable Not available in permanent magnet motor law Automatic whatever the load
acceleration and deceleration ramps Linear adjustable separately from 0.01 to 9000 s S, U or customized
braking to standstill By DC injection
protection type Thermal protection: motor Motor phase break: motor Thermal protection: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
frequency resolution Display unit: 0.1 Hz Analog input: 0.012/50 Hz
electrical connection Control, screw terminal: 0.5…1.5 mm² Line side, screw terminal: 2 x 50…3 x 120 mm² Motor, screw terminal: 3 x 50…3 x 120 mm²
connector type 1 RJ45 (on the remote graphic terminal) for Modbus serial
physical interface 2-wire RS 485 for Modbus serial
transmission frame RTU for Modbus serial
transmission rate 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
type of polarization No impedance for Modbus serial
number of addresses 1…247 for Modbus serial
method of access Slave
supply External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
local signalling 2 LEDs for local diagnostic 1 LED (yellow) for embedded communication status 2 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage
width 320 mm
height 852 mm 1159 mm with IP21 conformity kit
depth 390 mm
net weight 82 kg
analogue input number 3
analogue input type AI1, AI2, AI3 software-configurable voltage: 0…10 V DC, impedance: 30 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits AI2, AI3 software-configurable temperature probe or water level sensor
discrete input number 6
discrete input type DI1…DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
input compatibility DI1…DI6: logic input level 1 PLC conforming to EN/IEC 61131-2 DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68
discrete input logic Positive logic (source): DI1…DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1) Negative logic (sink): DI1…DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1) Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1)
analogue output number 2
analogue output type Software-configurable current AQ1, AQ2: 0…20 mA, resolution 10 bits Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bits
sampling duration 5 ms +/- 0.1 ms (AI1, AI2, AI3) – analog input 2 ms +/- 0.5 ms (DI1…DI6)configurable – discrete input 5 ms +/- 1 ms (DI5, DI6)configurable – pulse input 10 ms +/- 1 ms (AQ1, AQ2) – analog output
accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AQ1, AQ2: +/- 0.2 % for analog output
relay output number 3
relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC
maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
isolation Between power and control terminals
insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
noise level 76 dB conforming to 86/188/EEC
power dissipation in W 2026 W(forced convection) at 380 V, switching frequency 2.5 kHz
operating position Vertical +/- 10 degree
electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
pollution degree 2 conforming to EN/IEC 61800-5-1
vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
shock resistance 6 gn for 11 ms conforming to IEC 60068-2-27
relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
ambient air temperature for operation -15…45 °C (without derating) 45…60 °C (with derating factor)
operating altitude <= 1000 m without derating 1000…4800 m with current derating 1 % per 100 m
environmental characteristic Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3
standards EN/IEC 61800-3 Environment 2 category C3 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 60721-3
marking CE
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 96.344 kg
Package 1 Height 47 cm
Package 1 width 67 cm
Package 1 Length 103 cm

LC1F265M7

range of product Easy Altivar 610
product or component type Variable speed drive
product specific application Fan, pump, compressor, conveyor
device short name ATV610
variant Standard version
product destination Asynchronous motors
mounting mode Cabinet mount
EMC filter Integrated conforming to EN/IEC 61800-3 category C3 with 50 m
IP degree of protection IP20
type of cooling Forced convection
supply frequency 50…60 Hz +/-5 %
network number of phases 3 phases
[Us] rated supply voltage 380…460 V – 15…10 %
motor power kW 110 kW for normal duty 90 kW for heavy duty
motor power hp 150 hp for normal duty 125 hp for heavy duty
line current 201 A at 380 V (normal duty) 175.7 A at 460 V (normal duty) 170 A at 380 V (heavy duty) 149.1 A at 460 V (heavy duty)
prospective line Isc 50 kA
apparent power 140.0 kVA at 460 V (normal duty) 118.8 kVA at 460 V (heavy duty)
continuous output current 211 A at 2.5 kHz for normal duty 173 A at 2.5 kHz for heavy duty
maximum transient current 232 A during 60 s (normal duty) 260 A during 60 s (heavy duty)
asynchronous motor control profile Variable torque standard Optimized torque mode Constant torque standard
output frequency 0.0001…0.5 kHz
nominal switching frequency 2.5 kHz
switching frequency 1…8 kHz adjustable
number of preset speeds 16 preset speeds
communication port protocol Modbus serial
option card Slot A: communication card, Profibus DP V1 Slot A: digital or analog I/O extension card Slot A: relay output card
output voltage <= power supply voltage
motor slip compensation Can be suppressed Adjustable Not available in permanent magnet motor law Automatic whatever the load
acceleration and deceleration ramps Linear adjustable separately from 0.01 to 9000 s S, U or customized
braking to standstill By DC injection
protection type Thermal protection: motor Motor phase break: motor Thermal protection: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
frequency resolution Display unit: 0.1 Hz Analog input: 0.012/50 Hz
electrical connection Control, screw terminal: 0.5…1.5 mm² Line side, screw terminal: 2 x 50…3 x 120 mm² Motor, screw terminal: 3 x 50…3 x 120 mm²
connector type 1 RJ45 (on the remote graphic terminal) for Modbus serial
physical interface 2-wire RS 485 for Modbus serial
transmission frame RTU for Modbus serial
transmission rate 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
type of polarization No impedance for Modbus serial
number of addresses 1…247 for Modbus serial
method of access Slave
supply External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
local signalling 2 LEDs for local diagnostic 1 LED (yellow) for embedded communication status 2 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage
width 320 mm
height 852 mm 1159 mm with IP21 conformity kit
depth 390 mm
net weight 82 kg
analogue input number 3
analogue input type AI1, AI2, AI3 software-configurable voltage: 0…10 V DC, impedance: 30 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits AI2, AI3 software-configurable temperature probe or water level sensor
discrete input number 6
discrete input type DI1…DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
input compatibility DI1…DI6: logic input level 1 PLC conforming to EN/IEC 61131-2 DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68
discrete input logic Positive logic (source): DI1…DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1) Negative logic (sink): DI1…DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1) Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1)
analogue output number 2
analogue output type Software-configurable current AQ1, AQ2: 0…20 mA, resolution 10 bits Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bits
sampling duration 5 ms +/- 0.1 ms (AI1, AI2, AI3) – analog input 2 ms +/- 0.5 ms (DI1…DI6)configurable – discrete input 5 ms +/- 1 ms (DI5, DI6)configurable – pulse input 10 ms +/- 1 ms (AQ1, AQ2) – analog output
accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AQ1, AQ2: +/- 0.2 % for analog output
relay output number 3
relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC
maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
isolation Between power and control terminals
insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
noise level 76 dB conforming to 86/188/EEC
power dissipation in W 2026 W(forced convection) at 380 V, switching frequency 2.5 kHz
operating position Vertical +/- 10 degree
electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
pollution degree 2 conforming to EN/IEC 61800-5-1
vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
shock resistance 6 gn for 11 ms conforming to IEC 60068-2-27
relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
ambient air temperature for operation -15…45 °C (without derating) 45…60 °C (with derating factor)
operating altitude <= 1000 m without derating 1000…4800 m with current derating 1 % per 100 m
environmental characteristic Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3
standards EN/IEC 61800-3 Environment 2 category C3 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 60721-3
marking CE
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 96.344 kg
Package 1 Height 47 cm
Package 1 width 67 cm
Package 1 Length 103 cm

LC1F330M7

range of product Easy Altivar 610
product or component type Variable speed drive
product specific application Fan, pump, compressor, conveyor
device short name ATV610
variant Standard version
product destination Asynchronous motors
mounting mode Cabinet mount
EMC filter Integrated conforming to EN/IEC 61800-3 category C3 with 50 m
IP degree of protection IP20
type of cooling Forced convection
supply frequency 50…60 Hz +/-5 %
network number of phases 3 phases
[Us] rated supply voltage 380…460 V – 15…10 %
motor power kW 110 kW for normal duty 90 kW for heavy duty
motor power hp 150 hp for normal duty 125 hp for heavy duty
line current 201 A at 380 V (normal duty) 175.7 A at 460 V (normal duty) 170 A at 380 V (heavy duty) 149.1 A at 460 V (heavy duty)
prospective line Isc 50 kA
apparent power 140.0 kVA at 460 V (normal duty) 118.8 kVA at 460 V (heavy duty)
continuous output current 211 A at 2.5 kHz for normal duty 173 A at 2.5 kHz for heavy duty
maximum transient current 232 A during 60 s (normal duty) 260 A during 60 s (heavy duty)
asynchronous motor control profile Variable torque standard Optimized torque mode Constant torque standard
output frequency 0.0001…0.5 kHz
nominal switching frequency 2.5 kHz
switching frequency 1…8 kHz adjustable
number of preset speeds 16 preset speeds
communication port protocol Modbus serial
option card Slot A: communication card, Profibus DP V1 Slot A: digital or analog I/O extension card Slot A: relay output card
output voltage <= power supply voltage
motor slip compensation Can be suppressed Adjustable Not available in permanent magnet motor law Automatic whatever the load
acceleration and deceleration ramps Linear adjustable separately from 0.01 to 9000 s S, U or customized
braking to standstill By DC injection
protection type Thermal protection: motor Motor phase break: motor Thermal protection: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
frequency resolution Display unit: 0.1 Hz Analog input: 0.012/50 Hz
electrical connection Control, screw terminal: 0.5…1.5 mm² Line side, screw terminal: 2 x 50…3 x 120 mm² Motor, screw terminal: 3 x 50…3 x 120 mm²
connector type 1 RJ45 (on the remote graphic terminal) for Modbus serial
physical interface 2-wire RS 485 for Modbus serial
transmission frame RTU for Modbus serial
transmission rate 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
type of polarization No impedance for Modbus serial
number of addresses 1…247 for Modbus serial
method of access Slave
supply External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
local signalling 2 LEDs for local diagnostic 1 LED (yellow) for embedded communication status 2 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage
width 320 mm
height 852 mm 1159 mm with IP21 conformity kit
depth 390 mm
net weight 82 kg
analogue input number 3
analogue input type AI1, AI2, AI3 software-configurable voltage: 0…10 V DC, impedance: 30 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits AI2, AI3 software-configurable temperature probe or water level sensor
discrete input number 6
discrete input type DI1…DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
input compatibility DI1…DI6: logic input level 1 PLC conforming to EN/IEC 61131-2 DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68
discrete input logic Positive logic (source): DI1…DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1) Negative logic (sink): DI1…DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1) Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1)
analogue output number 2
analogue output type Software-configurable current AQ1, AQ2: 0…20 mA, resolution 10 bits Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bits
sampling duration 5 ms +/- 0.1 ms (AI1, AI2, AI3) – analog input 2 ms +/- 0.5 ms (DI1…DI6)configurable – discrete input 5 ms +/- 1 ms (DI5, DI6)configurable – pulse input 10 ms +/- 1 ms (AQ1, AQ2) – analog output
accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AQ1, AQ2: +/- 0.2 % for analog output
relay output number 3
relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC
maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
isolation Between power and control terminals
insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
noise level 76 dB conforming to 86/188/EEC
power dissipation in W 2026 W(forced convection) at 380 V, switching frequency 2.5 kHz
operating position Vertical +/- 10 degree
electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
pollution degree 2 conforming to EN/IEC 61800-5-1
vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
shock resistance 6 gn for 11 ms conforming to IEC 60068-2-27
relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
ambient air temperature for operation -15…45 °C (without derating) 45…60 °C (with derating factor)
operating altitude <= 1000 m without derating 1000…4800 m with current derating 1 % per 100 m
environmental characteristic Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3
standards EN/IEC 61800-3 Environment 2 category C3 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 60721-3
marking CE
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 96.344 kg
Package 1 Height 47 cm
Package 1 width 67 cm
Package 1 Length 103 cm

LC1F400M7

range of product Easy Altivar 610
product or component type Variable speed drive
product specific application Fan, pump, compressor, conveyor
device short name ATV610
variant Standard version
product destination Asynchronous motors
mounting mode Cabinet mount
EMC filter Integrated conforming to EN/IEC 61800-3 category C3 with 50 m
IP degree of protection IP20
type of cooling Forced convection
supply frequency 50…60 Hz +/-5 %
network number of phases 3 phases
[Us] rated supply voltage 380…460 V – 15…10 %
motor power kW 110 kW for normal duty 90 kW for heavy duty
motor power hp 150 hp for normal duty 125 hp for heavy duty
line current 201 A at 380 V (normal duty) 175.7 A at 460 V (normal duty) 170 A at 380 V (heavy duty) 149.1 A at 460 V (heavy duty)
prospective line Isc 50 kA
apparent power 140.0 kVA at 460 V (normal duty) 118.8 kVA at 460 V (heavy duty)
continuous output current 211 A at 2.5 kHz for normal duty 173 A at 2.5 kHz for heavy duty
maximum transient current 232 A during 60 s (normal duty) 260 A during 60 s (heavy duty)
asynchronous motor control profile Variable torque standard Optimized torque mode Constant torque standard
output frequency 0.0001…0.5 kHz
nominal switching frequency 2.5 kHz
switching frequency 1…8 kHz adjustable
number of preset speeds 16 preset speeds
communication port protocol Modbus serial
option card Slot A: communication card, Profibus DP V1 Slot A: digital or analog I/O extension card Slot A: relay output card
output voltage <= power supply voltage
motor slip compensation Can be suppressed Adjustable Not available in permanent magnet motor law Automatic whatever the load
acceleration and deceleration ramps Linear adjustable separately from 0.01 to 9000 s S, U or customized
braking to standstill By DC injection
protection type Thermal protection: motor Motor phase break: motor Thermal protection: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
frequency resolution Display unit: 0.1 Hz Analog input: 0.012/50 Hz
electrical connection Control, screw terminal: 0.5…1.5 mm² Line side, screw terminal: 2 x 50…3 x 120 mm² Motor, screw terminal: 3 x 50…3 x 120 mm²
connector type 1 RJ45 (on the remote graphic terminal) for Modbus serial
physical interface 2-wire RS 485 for Modbus serial
transmission frame RTU for Modbus serial
transmission rate 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
type of polarization No impedance for Modbus serial
number of addresses 1…247 for Modbus serial
method of access Slave
supply External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
local signalling 2 LEDs for local diagnostic 1 LED (yellow) for embedded communication status 2 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage
width 320 mm
height 852 mm 1159 mm with IP21 conformity kit
depth 390 mm
net weight 82 kg
analogue input number 3
analogue input type AI1, AI2, AI3 software-configurable voltage: 0…10 V DC, impedance: 30 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits AI2, AI3 software-configurable temperature probe or water level sensor
discrete input number 6
discrete input type DI1…DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
input compatibility DI1…DI6: logic input level 1 PLC conforming to EN/IEC 61131-2 DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68
discrete input logic Positive logic (source): DI1…DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1) Negative logic (sink): DI1…DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1) Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1)
analogue output number 2
analogue output type Software-configurable current AQ1, AQ2: 0…20 mA, resolution 10 bits Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bits
sampling duration 5 ms +/- 0.1 ms (AI1, AI2, AI3) – analog input 2 ms +/- 0.5 ms (DI1…DI6)configurable – discrete input 5 ms +/- 1 ms (DI5, DI6)configurable – pulse input 10 ms +/- 1 ms (AQ1, AQ2) – analog output
accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AQ1, AQ2: +/- 0.2 % for analog output
relay output number 3
relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC
maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
isolation Between power and control terminals
insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
noise level 76 dB conforming to 86/188/EEC
power dissipation in W 2026 W(forced convection) at 380 V, switching frequency 2.5 kHz
operating position Vertical +/- 10 degree
electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
pollution degree 2 conforming to EN/IEC 61800-5-1
vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
shock resistance 6 gn for 11 ms conforming to IEC 60068-2-27
relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
ambient air temperature for operation -15…45 °C (without derating) 45…60 °C (with derating factor)
operating altitude <= 1000 m without derating 1000…4800 m with current derating 1 % per 100 m
environmental characteristic Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3
standards EN/IEC 61800-3 Environment 2 category C3 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 60721-3
marking CE
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 96.344 kg
Package 1 Height 47 cm
Package 1 width 67 cm
Package 1 Length 103 cm

LC1F500M7

range of product Easy Altivar 610
product or component type Variable speed drive
product specific application Fan, pump, compressor, conveyor
device short name ATV610
variant Standard version
product destination Asynchronous motors
mounting mode Cabinet mount
EMC filter Integrated conforming to EN/IEC 61800-3 category C3 with 50 m
IP degree of protection IP20
type of cooling Forced convection
supply frequency 50…60 Hz +/-5 %
network number of phases 3 phases
[Us] rated supply voltage 380…460 V – 15…10 %
motor power kW 110 kW for normal duty 90 kW for heavy duty
motor power hp 150 hp for normal duty 125 hp for heavy duty
line current 201 A at 380 V (normal duty) 175.7 A at 460 V (normal duty) 170 A at 380 V (heavy duty) 149.1 A at 460 V (heavy duty)
prospective line Isc 50 kA
apparent power 140.0 kVA at 460 V (normal duty) 118.8 kVA at 460 V (heavy duty)
continuous output current 211 A at 2.5 kHz for normal duty 173 A at 2.5 kHz for heavy duty
maximum transient current 232 A during 60 s (normal duty) 260 A during 60 s (heavy duty)
asynchronous motor control profile Variable torque standard Optimized torque mode Constant torque standard
output frequency 0.0001…0.5 kHz
nominal switching frequency 2.5 kHz
switching frequency 1…8 kHz adjustable
number of preset speeds 16 preset speeds
communication port protocol Modbus serial
option card Slot A: communication card, Profibus DP V1 Slot A: digital or analog I/O extension card Slot A: relay output card
output voltage <= power supply voltage
motor slip compensation Can be suppressed Adjustable Not available in permanent magnet motor law Automatic whatever the load
acceleration and deceleration ramps Linear adjustable separately from 0.01 to 9000 s S, U or customized
braking to standstill By DC injection
protection type Thermal protection: motor Motor phase break: motor Thermal protection: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
frequency resolution Display unit: 0.1 Hz Analog input: 0.012/50 Hz
electrical connection Control, screw terminal: 0.5…1.5 mm² Line side, screw terminal: 2 x 50…3 x 120 mm² Motor, screw terminal: 3 x 50…3 x 120 mm²
connector type 1 RJ45 (on the remote graphic terminal) for Modbus serial
physical interface 2-wire RS 485 for Modbus serial
transmission frame RTU for Modbus serial
transmission rate 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
type of polarization No impedance for Modbus serial
number of addresses 1…247 for Modbus serial
method of access Slave
supply External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
local signalling 2 LEDs for local diagnostic 1 LED (yellow) for embedded communication status 2 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage
width 320 mm
height 852 mm 1159 mm with IP21 conformity kit
depth 390 mm
net weight 82 kg
analogue input number 3
analogue input type AI1, AI2, AI3 software-configurable voltage: 0…10 V DC, impedance: 30 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits AI2, AI3 software-configurable temperature probe or water level sensor
discrete input number 6
discrete input type DI1…DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
input compatibility DI1…DI6: logic input level 1 PLC conforming to EN/IEC 61131-2 DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68
discrete input logic Positive logic (source): DI1…DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1) Negative logic (sink): DI1…DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1) Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1)
analogue output number 2
analogue output type Software-configurable current AQ1, AQ2: 0…20 mA, resolution 10 bits Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bits
sampling duration 5 ms +/- 0.1 ms (AI1, AI2, AI3) – analog input 2 ms +/- 0.5 ms (DI1…DI6)configurable – discrete input 5 ms +/- 1 ms (DI5, DI6)configurable – pulse input 10 ms +/- 1 ms (AQ1, AQ2) – analog output
accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AQ1, AQ2: +/- 0.2 % for analog output
relay output number 3
relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC
maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
isolation Between power and control terminals
insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
noise level 76 dB conforming to 86/188/EEC
power dissipation in W 2026 W(forced convection) at 380 V, switching frequency 2.5 kHz
operating position Vertical +/- 10 degree
electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
pollution degree 2 conforming to EN/IEC 61800-5-1
vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
shock resistance 6 gn for 11 ms conforming to IEC 60068-2-27
relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
ambient air temperature for operation -15…45 °C (without derating) 45…60 °C (with derating factor)
operating altitude <= 1000 m without derating 1000…4800 m with current derating 1 % per 100 m
environmental characteristic Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3
standards EN/IEC 61800-3 Environment 2 category C3 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 60721-3
marking CE
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 96.344 kg
Package 1 Height 47 cm
Package 1 width 67 cm
Package 1 Length 103 cm

LC1F630M7

range of product Easy Altivar 610
product or component type Variable speed drive
product specific application Fan, pump, compressor, conveyor
device short name ATV610
variant Standard version
product destination Asynchronous motors
mounting mode Cabinet mount
EMC filter Integrated conforming to EN/IEC 61800-3 category C3 with 50 m
IP degree of protection IP20
type of cooling Forced convection
supply frequency 50…60 Hz +/-5 %
network number of phases 3 phases
[Us] rated supply voltage 380…460 V – 15…10 %
motor power kW 110 kW for normal duty 90 kW for heavy duty
motor power hp 150 hp for normal duty 125 hp for heavy duty
line current 201 A at 380 V (normal duty) 175.7 A at 460 V (normal duty) 170 A at 380 V (heavy duty) 149.1 A at 460 V (heavy duty)
prospective line Isc 50 kA
apparent power 140.0 kVA at 460 V (normal duty) 118.8 kVA at 460 V (heavy duty)
continuous output current 211 A at 2.5 kHz for normal duty 173 A at 2.5 kHz for heavy duty
maximum transient current 232 A during 60 s (normal duty) 260 A during 60 s (heavy duty)
asynchronous motor control profile Variable torque standard Optimized torque mode Constant torque standard
output frequency 0.0001…0.5 kHz
nominal switching frequency 2.5 kHz
switching frequency 1…8 kHz adjustable
number of preset speeds 16 preset speeds
communication port protocol Modbus serial
option card Slot A: communication card, Profibus DP V1 Slot A: digital or analog I/O extension card Slot A: relay output card
output voltage <= power supply voltage
motor slip compensation Can be suppressed Adjustable Not available in permanent magnet motor law Automatic whatever the load
acceleration and deceleration ramps Linear adjustable separately from 0.01 to 9000 s S, U or customized
braking to standstill By DC injection
protection type Thermal protection: motor Motor phase break: motor Thermal protection: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
frequency resolution Display unit: 0.1 Hz Analog input: 0.012/50 Hz
electrical connection Control, screw terminal: 0.5…1.5 mm² Line side, screw terminal: 2 x 50…3 x 120 mm² Motor, screw terminal: 3 x 50…3 x 120 mm²
connector type 1 RJ45 (on the remote graphic terminal) for Modbus serial
physical interface 2-wire RS 485 for Modbus serial
transmission frame RTU for Modbus serial
transmission rate 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
type of polarization No impedance for Modbus serial
number of addresses 1…247 for Modbus serial
method of access Slave
supply External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
local signalling 2 LEDs for local diagnostic 1 LED (yellow) for embedded communication status 2 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage
width 320 mm
height 852 mm 1159 mm with IP21 conformity kit
depth 390 mm
net weight 82 kg
analogue input number 3
analogue input type AI1, AI2, AI3 software-configurable voltage: 0…10 V DC, impedance: 30 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits AI2, AI3 software-configurable temperature probe or water level sensor
discrete input number 6
discrete input type DI1…DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
input compatibility DI1…DI6: logic input level 1 PLC conforming to EN/IEC 61131-2 DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68
discrete input logic Positive logic (source): DI1…DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1) Negative logic (sink): DI1…DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1) Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1)
analogue output number 2
analogue output type Software-configurable current AQ1, AQ2: 0…20 mA, resolution 10 bits Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bits
sampling duration 5 ms +/- 0.1 ms (AI1, AI2, AI3) – analog input 2 ms +/- 0.5 ms (DI1…DI6)configurable – discrete input 5 ms +/- 1 ms (DI5, DI6)configurable – pulse input 10 ms +/- 1 ms (AQ1, AQ2) – analog output
accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AQ1, AQ2: +/- 0.2 % for analog output
relay output number 3
relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC
maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
isolation Between power and control terminals
insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
noise level 76 dB conforming to 86/188/EEC
power dissipation in W 2026 W(forced convection) at 380 V, switching frequency 2.5 kHz
operating position Vertical +/- 10 degree
electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
pollution degree 2 conforming to EN/IEC 61800-5-1
vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
shock resistance 6 gn for 11 ms conforming to IEC 60068-2-27
relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
ambient air temperature for operation -15…45 °C (without derating) 45…60 °C (with derating factor)
operating altitude <= 1000 m without derating 1000…4800 m with current derating 1 % per 100 m
environmental characteristic Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3
standards EN/IEC 61800-3 Environment 2 category C3 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 60721-3
marking CE
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 96.344 kg
Package 1 Height 47 cm
Package 1 width 67 cm
Package 1 Length 103 cm

فروشگاه