رله کنترل فاز

فیلترها

دسته‌بندی را انتخاب کنید

RM17TE00

Main
range of productHarmony Control Relays
product or component type3-phase control relay
relay typeMultifunction control relay
product specific applicationFor 3-phase supply
relay nameRM17TE
relay monitored parametersUndervoltage and overvoltage in window mode
Asymmetry
Phase sequence
Phase failure detection
time delayAdjustable 0.1…10 s, +/- 10 % of the full scale value
switching capacity in VA1250 VA
measurement range208…480 V voltage AC
contacts type and composition1 C/O
[Uc] control circuit voltage208…480 V
Complementary
reset time1500 ms time delay
maximum switching voltage250 V AC
250 V DC
minimum switching current10 mA at 5 V DC
maximum switching current5 A AC
5 A DC
supply voltage limits183…528 V AC
control circuit voltage limits– 12 % + 10 % Un
power consumption in VA0…22 VA at 400 V AC 50 Hz
control circuit frequency50…60 Hz +/- 10 %
output contacts1 C/O
nominal output current5 A
measurement voltage limits183…528 V AC
hysteresis2 %
delay at power up650 ms
maximum measuring cycle150 ms measurement cycle as true rms value
threshold adjustment voltage-2…-17 % in the range 220 V AC
+2…+17 % in the range 480 V AC
-2…-12 % in the range 208 V AC
2…20 % of Un selected
voltage range208…480 V phase to phase
adjustment of asymmetry threshold5…15 % of Un selected
repeat accuracy0.5 % for input and measurement circuit
3 % for time delay
measurement error< 0.05 %/°C with temperature variation
< 1 % over the whole range with voltage variation
phase failure sensitivity0.7 Un
response time< 200 ms (in the event of a fault)
markingCE
overvoltage categoryIII conforming to IEC 60664-1
insulation resistance> 500 MOhm at 500 V DC conforming to IEC 60255-5
> 500 MOhm at 500 V DC conforming to IEC 60664-1
[Ui] rated insulation voltage400 V conforming to IEC 60664-1
supply frequency50/60 Hz +/- 10 %
operating positionAny position without derating
connections – terminalsScrew terminals, 1 x 0.5…1 x 4 mm² (AWG 20…AWG 11) solid without cable end
Screw terminals, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) solid without cable end
Screw terminals, 1 x 0.2…1 x 2.5 mm² (AWG 24…AWG 12) flexible with cable end
Screw terminals, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16) flexible with cable end
tightening torque0.6…1 N.m conforming to IEC 60947-1
housing materialSelf-extinguishing plastic
local signallingLED (green) for power ON
LED (yellow) for relay ON
mounting support35 mm symmetrical DIN rail conforming to EN/IEC 60715
electrical durability100000 cycles
mechanical durability30000000 cycles
operating rate<= 360 operations/hour full load
utilisation categoryAC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
safety reliability dataMTTFd = 502.2 years
B10d = 470000
width17.5 mm
net weight0.13 kg
Environment
electromagnetic compatibilityEmission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
Immunity for industrial environments conforming to EN/IEC 61000-6-2
standardsEN/IEC 60255-1
product certificationsGOST
C-Tick
CSA
UL
GL
directives89/336/EEC – electromagnetic compatibility
73/23/EEC – low voltage directive
ambient air temperature for storage-40…70 °C
ambient air temperature for operation-20…50 °C
relative humidity95 % at 55 °C conforming to IEC 60068-2-30
vibration resistance0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6
1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
shock resistance15 gn for 11 ms conforming to IEC 60255-21-1
IP degree of protectionIP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
pollution degree3 conforming to IEC 60664-1
dielectric test voltage2 kV, 1 min AC 50 Hz conforming to IEC 60255-5
2 kV, 1 min AC 50 Hz conforming to IEC 60664-1
non-dissipating shock wave4 kV conforming to IEC 60255-5
4 kV conforming to IEC 60664-1
4 kV conforming to IEC 61000-4-5

RM17TG20

Main
range of productHarmony Control Relays
product or component type3-phase control relay
relay typeControl relay
product specific applicationFor 3-phase supply
relay nameRM17TG
relay monitored parametersPhase sequence
Phase failure detection (2 or more phase cut)
time delayWithout
switching capacity in VA1250 VA
measurement range208…440 V voltage AC
contacts type and composition2 C/O
[Uc] control circuit voltage208…440 V
Complementary
maximum switching voltage250 V AC
250 V DC
minimum switching current10 mA at 5 V DC
supply voltage limits183…484 V AC
control circuit voltage limits– 12 % + 10 % Un
power consumption in VA0…22 VA at 400 V AC 50 Hz
voltage detection threshold< 100 V AC
control circuit frequency50…60 Hz +/- 10 %
output contacts2 C/O
nominal output current5 A
measurement voltage limits183…484 V AC
delay at power up650 ms
voltage range183…484 V
response time<= 130 ms (in the event of a fault)
markingCE
overvoltage categoryIII conforming to IEC 60664-1
insulation resistance> 500 MOhm at 500 V DC conforming to IEC 60255-5
> 500 MOhm at 500 V DC conforming to IEC 60664-1
[Ui] rated insulation voltage400 V conforming to IEC 60664-1
supply frequency50/60 Hz +/- 10 %
operating positionAny position without derating
connections – terminalsScrew terminals, 1 x 0.5…1 x 4 mm² (AWG 20…AWG 11) solid without cable end
Screw terminals, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) solid without cable end
Screw terminals, 1 x 0.2…1 x 2.5 mm² (AWG 24…AWG 12) flexible with cable end
Screw terminals, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16) flexible with cable end
tightening torque0.6…1 N.m conforming to IEC 60947-1
housing materialSelf-extinguishing plastic
local signallingLED (yellow) for relay ON
mounting support35 mm symmetrical DIN rail conforming to EN/IEC 60715
electrical durability10000 cycles
mechanical durability30000000 cycles
operating rate<= 360 operations/hour full load
utilisation categoryAC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
safety reliability dataB10d = 850000
MTTFd = 924.6 years
width17.5 mm
net weight0.13 kg
Environment
electromagnetic compatibilityEmission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
Immunity for industrial environments conforming to EN/IEC 61000-6-2
standardsEN/IEC 60255-1
product certificationsGOST
C-Tick
UL
CSA
GL
directives73/23/EEC – low voltage directive
89/336/EEC – electromagnetic compatibility
ambient air temperature for storage-40…70 °C
ambient air temperature for operation-20…50 °C
relative humidity95 % at 55 °C conforming to IEC 60068-2-30
vibration resistance0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6
1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
shock resistance15 gn for 11 ms conforming to IEC 60255-21-1
IP degree of protectionIP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
pollution degree3 conforming to IEC 60664-1
dielectric test voltage2 kV, 1 min AC 50 Hz
non-dissipating shock wave4 kV

RM35TF30

Main
range of productHarmony Control Relays
product or component type3-phase control relay
relay typeMultifunction control relay
product specific applicationFor 3-phase supply
relay nameRM35TF
relay monitored parametersUndervoltage and overvoltage in window mode
Phase sequence
Phase failure detection
Asymmetry
time delayAdjustable 0.1…10 s, +/- 10 % of the full scale value
switching capacity in VA1250 VA
measurement range220…480 V voltage AC
contacts type and composition2 C/O
[Uc] control circuit voltage220…480 V
Complementary
reset time1500 ms at 480 V
maximum switching voltage250 V AC
250 V DC
minimum switching current10 mA at 5 V DC
maximum switching current5 A AC
5 A DC
supply voltage limits194…528 V AC, 3 phases
control circuit voltage limits– 12 % + 10 % Un
power consumption in VA0…22 VA at 400 V AC 50 Hz
voltage detection threshold< 194 V
control circuit frequency50…60 Hz +/- 10 %
output contacts2 C/O
nominal output current5 A
measurement voltage limits176…528 V AC
hysteresis2 %
delay at power up650 ms
maximum measuring cycle140 ms measurement cycle as true rms value
threshold adjustment voltage-20…-2 % in the range 380…480 V AC
2…20 % of Un selected
-12…-2 % in the range 220 V AC
+2…+20 % in the range 220…440 V AC
+2…+10 % in the range 480 V AC
voltage range220…480 V phase to phase
adjustment of asymmetry threshold5…15 % of Un selected
repeat accuracy0.3 % for time delay
0.5 % for input and measurement circuit
measurement error< 1 % over the whole range with voltage variation
0.05 %/°C with temperature variation
response time< 200 ms (in the event of a fault)
markingCE
overvoltage categoryIII conforming to IEC 60664-1
insulation resistance> 500 MOhm at 500 V DC conforming to IEC 60255-5
> 500 MOhm at 500 V DC conforming to IEC 60664-1
[Ui] rated insulation voltage400 V conforming to IEC 60664-1
supply frequency50/60 Hz +/- 10 %
operating positionAny position without derating
connections – terminalsScrew terminals, 1 x 0.5…1 x 4 mm² (AWG 20…AWG 11) solid without cable end
Screw terminals, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) solid without cable end
Screw terminals, 1 x 0.2…1 x 2.5 mm² (AWG 24…AWG 12) flexible with cable end
Screw terminals, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16) flexible with cable end
tightening torque0.6…1 N.m conforming to IEC 60947-1
housing materialSelf-extinguishing plastic
local signallingLED (green) for power ON
LED (yellow) for relay ON
LED (yellow) for fault
mounting support35 mm symmetrical DIN rail conforming to EN/IEC 60715
electrical durability100000 cycles
mechanical durability30000000 cycles
operating rate<= 360 operations/hour full load
utilisation categoryAC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
safety reliability dataMTTFd = 399.5 years
B10d = 360000
width35 mm
net weight0.13 kg
Environment
electromagnetic compatibilityEmission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
Immunity for industrial environments conforming to EN/IEC 61000-6-2
standardsEN/IEC 60255-1
product certificationsGL
UL
CSA
GOST
C-Tick
directives89/336/EEC – electromagnetic compatibility
73/23/EEC – low voltage directive
ambient air temperature for storage-40…70 °C
ambient air temperature for operation-20…50 °C
relative humidity95 % at 55 °C conforming to IEC 60068-2-30
vibration resistance0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6
1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
shock resistance15 gn for 11 ms conforming to IEC 60255-21-1
IP degree of protectionIP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
pollution degree3 conforming to IEC 60664-1
dielectric test voltage2 kV, 1 min AC 50 Hz
non-dissipating shock wave4 kV

فروشگاه